Monitor data – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 395

Advertising
background image

Register No.

Contents

000FH

Control Selection Setting
bit 0

Reserved

bit 1

PID Setpoint Input

bit 2

Torque reference / torque limit input (enables the setting from MEMOBUS/Modbus)

bit 3

Torque compensation input (enables the setting from MEMOBUS/Modbus)

bit 4 to B

Reserved

bit C

Enable Terminal S5 Input for Broadcast Data

bit D

Enable Terminal S6 Input for Broadcast Data

bit E

Enable Terminal S7 Input for Broadcast Data

bit F

Enable Terminal S8 Input for Broadcast Data

0010H to 001AH

Reserved

001BH

Analog Monitor Option AO-A3 Analog Output 1 (10 V/4000 H)

001CH

Analog Monitor Option AO-A3 Analog Output 2 (10 V/4000 H)

001DH

Digital Output Option DO-A3 Output (Binary)

001EH to 001FH

Reserved

u

Monitor Data

Monitor data can be read only.

Register No.

Contents

0020H

Drive Status 1
bit 0

During Run

bit 1

During Reverse

bit 2

Drive Ready

bit 3

Fault

bit 4

Data Setting Error

bit 5

Multi-Function Contact Output 1 (terminal M1-M2)

bit 6

Multi-Function Contact Output 2 (terminal M3-M4)

bit 7

Multi-Function Contact Output 3 (terminal MD-ME-MF)

bit 8 to bit D

Reserved

bit E

When ComRef has been enabled

bit F

When ComCtrl has been enabled

D.9 MEMOBUS/Modbus Data Table

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

395

D

MEMOBUS/Modbus Communications