3.4 Input and Output Power Wiring Connections

The input disconnect switch is located in the upper right hand side of the bypass. The three-phase input power connection is

made to the input terminals of the disconnect. Refer to

Figure 3.8

for a representative example.

The Overload Relay (OLR) is mounted to the contactor assembly or back panel (depending on rating), just above the bypass

contactor. The bypass three-phase output power connection to the motor is made to the output terminals of the Overload Relay.

C

G

E

F

A

B

D

H

I

A – Ground screw
B – Input power terminals
C – Motor overload relay
D – Motor connections
E – Drive output contactor K2

F – Bypass contactor K3
G – 120 V control transformer
H – A2 bypass control board
I – 5 V bypass power supply board

Figure 3.8 Bypass Circuit Components

u

Factory Recommended Branch Circuit Protection

WARNING! Fire Hazard. Branch Circuit protection is required to be installed according to applicable local codes and the requirements listed

on the bypass nameplate. Failure to comply could result in fire and damage to the bypass and drive or injury to personnel. Bypass models

without soft-starter option PW are suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical amperes, 208

Vac and 480 Vac. Bypass models D169 to D211 and B180 to B414 with option PW are also suitable for use on a circuit capable of delivering

not more than 100,000 RMS symmetrical amperes, 208 Vac and 480 Vac. Bypass models D024 to D143 and B011 to B156 with option PW

are suitable for use on a circuit capable of delivering not more than 65,000 RMS symmetrical amperes, 208 Vac and 480 Vac.

Yaskawa recommends installing branch circuit protection according to maintain compliance with UL508C. Semiconductor

protective type fuses are preferred. Alternate branch circuit protection devices are also listed in this manual.

3.4 Input and Output Power Wiring Connections

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

85