C4: torque compensation, C6: carrier frequency, Configuration, reduce the ground currents – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 154

Advertising
background image

C2-02

C2-01

0.20 s

<1>

0.20 s

<1>

C2-02

C2-01

0.20 s

<1>

0.20 s

<1>

FWD run

REV run

Output
frequency

<1> S-Curve characteristic at Decel Start/End is fixed to 0.20 s.

Figure 5.14 S-Curve Timing Diagram - FWD/REV Operation

Setting the S-curve will increase the acceleration and deceleration times.
Actual accel time = accel time setting + (C2-01 + C2-02) / 2

u

C4: Torque Compensation

The torque compensation function compensates for insufficient torque production at start-up or when a load is applied.

Note:

Set the motor parameters and V/f pattern properly before setting torque compensation parameters.

n

C4-01: Torque Compensation Gain

Sets the gain for the torque compensation function.

No.

Parameter Name

Setting Range

Default

C4-01

Torque Compensation Gain

0.00 to 2.50

1.00

Torque Compensation:

The drive calculates the motor primary voltage loss using the output current and the termination resistor value (E2-05) and

adjusts the output voltage to compensate insufficient torque at start or when load is applied. The effects of this voltage

compensation can be increased or decreased using parameter C4-01.

Adjustment

Although this parameter rarely needs to be changed, it may be necessary to adjust the torque compensation gain in small steps

of 0.05 in the following situations:
• Increase this setting when using a long motor cable.
• Decrease this setting when motor oscillation occurs.
Adjust C4-01 so the output current does not exceed the drive rated current.

u

C6: Carrier Frequency

n

C6-02: Carrier Frequency Selection

Sets the switching frequency of the drive output transistors. Changes to the switching frequency lower audible noise and reduce

leakage current.

Note:

Increasing the carrier frequency above the default value automatically lowers the drive current rating.

No.

Parameter Name

Setting Range

Default

C6-02

Carrier Frequency Selection

1 to 4

Determined by o2-04

Setting 1: 4.0 kHz
Setting 2: 6.0 kHz
Setting 3: 8.0 kHz
Setting 4: 10.0 kHz

5.3 C: Tuning

154

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual