Figure 5.55, 14 z: bypass parameters – Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 211

Run Delay with Preset Speed Examples
VFD RUN COMMAND
VFD OUTPUT FREQUENCY
DAMPER ACTUATOR OUTPUT
BAS INTERLOCK INPUT
t1
t2
t3
VFD FREQUENCY REFERENCE
Parameter Settings:
Z1-12 Run Delay Time = 0.0 sec
Z1-13 Pre Int Run Sel = 0 (Disabled)
Z1-14 Run Delay Fref = 60.0 Hz
Z1-15 Interlck Wait Tm = 0.0 sec (Never Time Out)
Figure 5.55 Run Delay with Preset Speed Example: Default Setting
VFD RUN COMMAND
VFD OUTPUT FREQUENCY
DAMPER ACTUATOR OUTPUT
BAS INTERLOCK INPUT
2
t
1
t
VFD FREQUENCY REFERENCE
Parameter Settings:
Z1-12 Run Delay Time = 0.0 sec
Z1-13 Pre Int Run Sel = 0 (Disabled)
Z1-14 Run Delay Fref = 60.0 Hz
Z1-15 Interlck Wait Tm = 10.0 sec
Z1-15 Interlck Wait Tm
t3
FAULT: FB02 BAS Ilock Open
Figure 5.56 Run Delay with Preset Speed Example: BAS Interlock Wait Time Fault
5.14 Z: Bypass Parameters
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual
211
5
Programming