Run Delay with Preset Speed Examples

VFD RUN COMMAND

VFD OUTPUT FREQUENCY

DAMPER ACTUATOR OUTPUT

BAS INTERLOCK INPUT

t1

t2

t3

VFD FREQUENCY REFERENCE

Parameter Settings:
Z1-12 Run Delay Time = 0.0 sec
Z1-13 Pre Int Run Sel = 0 (Disabled)
Z1-14 Run Delay Fref = 60.0 Hz
Z1-15 Interlck Wait Tm = 0.0 sec (Never Time Out)

Figure 5.55 Run Delay with Preset Speed Example: Default Setting

VFD RUN COMMAND

VFD OUTPUT FREQUENCY

DAMPER ACTUATOR OUTPUT

BAS INTERLOCK INPUT

2

t

1

t

VFD FREQUENCY REFERENCE

Parameter Settings:
Z1-12 Run Delay Time = 0.0 sec
Z1-13 Pre Int Run Sel = 0 (Disabled)
Z1-14 Run Delay Fref = 60.0 Hz
Z1-15 Interlck Wait Tm = 10.0 sec

Z1-15 Interlck Wait Tm

t3

FAULT: FB02 BAS Ilock Open

Figure 5.56 Run Delay with Preset Speed Example: BAS Interlock Wait Time Fault

5.14 Z: Bypass Parameters

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual