Z1-34: Loss of Load Drive Time

While in Drive mode, the Loss of Load detection conditions must be met for the length of time entered here before detecting

a loss of load.

No.

Name

Setting Range

Default

Z1-34

Loss of Load Drive Time

0.0 to 300.0 s

1.0 s

n

Z1-35: Loss of Load Bypass Output Current

The motor current must be equal to or less than this value to detect a loss of load.

No.

Name

Setting Range

Default

Z1-35

Loss of Load Bypass Output Current

0.0 to 999.9

0.0 A

n

Z1-36: Loss of Load Bypass Time

While in Bypass mode, the Loss of Load detection conditions must be met for the length of time entered here before detecting

a loss of load.

No.

Name

Setting Range

Default

Z1-36

Loss of Load Bypass Time

0.0 to 300.0

1.0 s

n

Z1-37: Set Time

Changes the LCD display to time setting to set the Real Time Clock.

No.

Name

Setting Range

Default

Z1-37

Set Time

0 to 2

0

Setting 0: Normal Display
Setting 1: Displays Time and Date Setting Mode
Setting 2: Reset Time

n

Z1-38: HOA Source Select

No.

Name

Setting Range

Default

Z1-38

HOA Source Select

0 to 2

0

Setting 0: Operator

The HOA keypad controls the HAND/OFF/AUTO commands.

Setting 1: Digital Inputs

The H1-oo multi-function digital input parameters control the HAND/OFF/AUTO commands.

Setting 2: Serial Communications

The serial communications protocol selected in parameter Z3-01 control the HAND/OFF/AUTO commands.

n

Z1-39: Drive/Bypass Source Select

No.

Name

Setting Range

Default

Z1-39

Drive/Bypass Source Select

0 to 2

0

Setting 0: Operator

The HOA keypad selects the Drive or Bypass as the source.

Setting 1: Digital Inputs

The H1-oo multi-function digital input parameters select the Drive or Bypass as the source.

Setting 2: Serial Communications

The serial communications protocol selected in parameter Z3-01 selects the Drive or Bypass as the source.

n

Z1-40: Auto Transfer Wait Time

Sets the length of time that the bypass controller will wait before switching to bypass when Auto Transfer is enabled and a

drive fault is detected.

5.14 Z: Bypass Parameters

214

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual