Contents

00C2H

Fault Contents 5
bit 0

MEMOBUS/Modbus Communication Error (CE)

bit 1

Option Communication Error (bUS)

bit 2, 3

Reserved

bit 4

Control Fault (CF)

bit 5

Zero Servo Fault (SvE)

bit 6

Option Card External Fault (EF0)

bit 7

PID Feedback Loss (FbL)

bit 8

Undertorque Detection 1 (UL3)

bit 9

Undertorque Detection 2 (UL4)

bit A to E

Reserved

bit F

Hardware Fault (includes oFx)

00C3H

Fault Contents 6
bit 0

Reserved

bit 1

Z Pulse Fault (dv1)

bit 2

Z Pulse Noise Fault Detection (dv2)

bit 3

Inversion Detection (dv3)

bit 4

Inversion Prevention Detection (dv4)

bit 5

Output Current Imbalance (LF2)

bit 6

Pull-Out Detection (STo)

bit 7

PG Hardware Fault (PGoH)

bit 8

MECHATROLINK Watchdog Timer Error (E5)

bit 9

Reserved

bit A

Too Many Speed Search Restarts (SEr)

bit B to F

Reserved

00C4H

Fault Contents 7
bit 0

PID Feedback Loss (FbH)

bit 1

External Fault 1, input terminal S1 (EF1)

bit 2

External Fault 2, input terminal S2 (EF2)

bit 3

Mechanical Weakening Detection 1 (oL5)

bit 4

Mechanical Weakening Detection 2 (UL5)

bit 5

Current Offset Fault (CoF)

bit 6, 7

Reserved

bit 8

DriveWorksEZ Fault (dWFL)

bit 9 to F

Reserved

00C5H

Fault Contents 8
bit 0

LSo Fault (LSo)

bit 1

CanOpenNID Error (nSE)

bit 2 to 9

Reserved

bit A

Initial Polarity Estimation Timeout (dv7)

bit B to F

Reserved

00C6H to 00C7H

Reserved

D.9 MEMOBUS/Modbus Data Table