H2: multi-function digital outputs – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 167

Advertising
background image

Setting 19: PID Disable

Close a digital input to indefinitely disable the PID function. When the input is released, the drive resumes PID operation.

Refer to PID Block Diagram on page 145

.

Setting 24: External Fault

The External fault command stops the drive when problems occur with external devices.
To use the External fault command, set one of the multi-function digital inputs to 24. The HOA keypad will display EFo

where o is the number of the terminal to which the external fault signal is assigned.
For example, if an external fault signal is input to terminal DI-3, “EF3” will be displayed.
The conditions of setting 24 are:
• Terminal status is normally open
• Detection condition is always detected
• Stopping method is coast to stop.

Setting 60: Motor Pre-Heat 1

A DC current can be circulated through the motor windings to create heat and prevent moisture from condensing on the wire.
Motor Pre-Heating can only be initiated by closing a digital input programmed as a Motor Pre-Heat input (H1-oo = 60). The

level of the DC current used by the Motor Pre-Heat function is determined by b2-09.
A Run input will be given priority over a Motor Pre-Heat input and when the Run command is removed, the motor pre-heating

will resume if the Motor Pre-Heat input is still closed.

Motor Pre-Heat 1

command

FWD Run command

Output frequency

Motor Pre-Heat 1

Motor Pre-Heat 1
braking

Motor Pre-Heat 1

Start Frequency

(b2-01)

OFF

OFF

OFF

OFF

ON

ON

Figure 5.19 Motor Pre-Heat 1 Input Timing Diagram

u

H2: Multi-Function Digital Outputs

n

H2-01 to H2-03: Terminal M1-M2, M3-M4, and MD-ME-MF Function Selection

The drive has three multi-function output terminals.

Table 5.22

lists the functions available for theses terminals using H2-01,

H2-02, and H2-03.

No.

Parameter Name

Setting Range

Default

H2-01

Terminal M1-M2 Function Selection (relay)

0 to 164

0: During Run

H2-02

Terminal M3-M4 Function Selection (relay)

0 to 164

1: Zero Speed

H2-03

Terminal MD-ME-MF Function Selection (relay)

0 to 164

2: Speed Agree 1

Table 5.22 Multi-Function Digital Output Terminal Settings

Setting

Function

Page

0

During Run 1

168

1

Zero Speed

168

2

Speed Agree 1

168

3

User-Set Speed Agree 1

169

4

Frequency Detection 1

169

5

Frequency Detection 2

170

6

Drive Ready

170

7

DC Bus Undervoltage

170

8

During Baseblock 1 (N.O.)

170

Setting

Function

Page

B

Torque Detection 1 (N.O.)

171

C

Frequency Reference Loss

171

E

Fault

171

F

Through Mode

171

10

Minor Fault

171

11

Fault Reset Command Active

171

13

Speed Agree 2

171

14

User-Set Speed Agree 2

171

15

Frequency Detection 3

172

5.7 H: Terminal Functions

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

167

5

Programming