b3-52

Motor speed

Output frequency

Power supply voltage

0

Momentary power loss time t

Normal operation

Search in progress

b3-50

b3-51

Forward operation

t

Figure 5.7 Speed Search from Forward Run Command

Continuous Baseblock (b3-50 ≤ t < b3-51)

When time t from the momentary power loss to recovery is between the times set for b3-50 and b3-51, operation will not be

restarted and the baseblock will continue. The drive will stay in baseblock for the time set in b3-51 even after restoring power.

After the time set in b3-51 passes, Speed Search starts in the opposite direction of the direction command. The deceleration

time in b3-53 is used for the search frequency and the setting value of the maximum frequency is used as the starting search

frequency.

Motor speed

Output frequency

Power supply voltage

0

Normal operation

Search in progress

b3-50

b3-51

b3-53

Forward operation

t

Momentary power loss time t

Figure 5.8 Continuing Baseblock

Speed Search in Direction Opposite to Direction Command (b3-51 ≤ t)

When time t from the momentary power loss to recovery exceeds the setting value of b3-51, Speed Search is performed in the

opposite direction of the direction command. The deceleration time in b3-53 is used for the search frequency and the setting

value of the maximum frequency is used as the starting search frequency.

5.2 b: Application

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

141