Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 290
Advertising
3.
Release the cables from the hooks in five locations.
A
A –Hook locations
Figure 7.12 Release the Cables
4.
Loosen the four screws affixing the cooling fan unit.
A
A –Screw locations
Figure 7.13 Remove the Cooling Fan Unit
5.
Disconnect the three pluggable connectors and remove the fan unit from the drive.
Figure 7.14 Unplug the Relay Connectors
n
Installing the Cooling Fan Unit
1.
Connect the relay connectors for the fans in the replacement fan unit.
Note:
Replace the whole unit when performing maintenance on the cooling fans.
7.5 Drive Cooling Fans