Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 397

Advertising
background image

Register No.

Contents

002AH

Alarm Contents 1
bit 0, 1

Reserved

bit 2

Forward/Reverse Run Command Input Error (EF)

bit 3

Baseblock (bb)

bit 4

Overtorque 1 (oL3)

bit 5

Heatsink Overheat (oH)

bit 6

Control Circuit Overvoltage (ov)

bit 7

Control Circuit Undervoltage (Uv)

bit 8

Fan Fault (FAn)

bit 9

MEMOBUS/Modbus Communication Error (CE)

bit A

Option Communication Error (bUS)

bit B

Undertorque Detection 1/2 (UL3/UL4)

bit C

Motor Overheat (oH3)

bit D

PID Feedback Loss, Excessive PID Feedback (FbL, FbH)

bit E

Reserved

bit F

Serial Communication Transmission Error (CALL)

002BH

Input Terminal Status
bit 0

Terminal S1 Closed

bit 1

Terminal S2 Closed

bit 2

Terminal S3 Closed

bit 3

Terminal S4 Closed

bit 4

Terminal S5 Closed

bit 5

Terminal S6 Closed

bit 6

Terminal S7 Closed

bit 7

Terminal S8 Closed

bit 8 to bit F

Reserved

002CH

Drive Status 2
bit 0

During Run

bit 1

Zero Speed

bit 2

Speed Agree

bit 3

User-set Speed Agree

bit 4

Frequency Detection 1

bit 5

Frequency Detection 2

bit 6

Drive Ready

bit 7

During Undervoltage

bit 8

During Baseblock

bit 9

Frequency Reference from Operator Keypad

bit A

Run Command from Operator Keypad

bit B

Over/Undertorque Detection 1, 2

bit C

Frequency Reference Loss

bit D

During Fault Restart

bit E

Fault

bit F

Communication Timeout

002DH

Output Terminal Status
bit 0

Multi-Function Contact Output 1 (terminal M1-M2)

bit 1

Multi-Function Contact Output 2 (terminal M3-M4)

bit 2

Multi-Function Contact Output 3 (terminal MD-ME-MF)

bit 3 to 6

Reserved

bit 7

Fault Contact Output (terminal MA/MB-MC)

bit 8 to F

Reserved

D.9 MEMOBUS/Modbus Data Table

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

397

D

MEMOBUS/Modbus Communications