Binary output objects, Binary value objects – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 372

Advertising
background image

Object ID

Object Name

Modbus

Address

Active Text

Inactive Text

PV Access

BI17

BYP DI-8 STAT

8781H: bit 7

ON

OFF

R

BI18

BYP DO-1 STAT

8782H: bit 0

ON

OFF

R

BI19

BYP DO-2 STAT

8782H: bit 1

ON

OFF

R

BI20

BYP DO-3 STAT

8782H: bit 2

ON

OFF

R

BI21

BYP DO-4 STAT

8782H: bit 3

ON

OFF

R

BI22

BYP DO-5 STAT

8782H: bit 4

ON

OFF

R

BI23

BYP DO-6 STAT

8782H: bit 5

ON

OFF

R

BI24

BYP DO-7 STAT

8782H: bit 6

ON

OFF

R

BI25

BYP DO-8 STAT

8782H: bit 7

ON

OFF

R

BI26

BYP DO-9 STAT

8783H: bit 0

ON

OFF

R

BI27

BYP DO-10 STAT

8783H: bit 1

ON

OFF

R

u

Binary Output Objects

Table C.8 Binary Output Objects

Object ID

Object Name

Modbus

Address

Active Text

Inactive Text

PV Access

BO1

MF Output M1-M2

0009H:bit 0

ON

OFF

C

BO2

MF Output M3-M4

0009H:bit 1

ON

OFF

C

BO3

MF Output M5-M6

0009H:bit 2

ON

OFF

C

BO4

Ref Sel: PID Setpoint

000FH:bit 1

ON

OFF

C

BO5

Ref Sel: Term S5 IN

8480H:bit 8

ON

OFF

C

BO6

Ref Sel: Term S6 IN

8480H:bit 9

ON

OFF

C

BO7

Refl Sel: Term S7 IN

8480H:bit 10

ON

OFF

C

BO8

BYP DO-07 COMMAND

8403H:bit 6

ON

OFF

C

BO9

BYP DO-08 COMMAND

8403H:bit 7

ON

OFF

C

B010

BYP DO-09 COMMAND

8403H:bit 8

ON

OFF

C

B011

BYP DO-10 COMMAND

8403H:bit 9

ON

OFF

C

u

Binary Value Objects

Table C.9 Binary Value Objects

Object ID

Object Name

Modbus

Address

Active Text

Inactive Text

PV Access

BV1

Not Used BV1

–

–

–

–

BV2

Not Used BV2

–

–

–

–

BV3

Ext Fault Cmd

8480H:bit 2

FAULT

OFF

C

BV4

Fault Reset Cmd

8480H:bit 3

RESET

OFF

C

BV5

Not Used BV5

–

–

–

–

BV6

Not Used BV6

–

–

–

–

BV7

MF Input 3 Cmd

8480H:bit 6

ON

OFF

C

BV8

MF Input 4 Cmd

8480H:bit 7

ON

OFF

C

BV9

MF Input 5 Cmd

8480H:bit 8

ON

OFF

C

BV10

MF Input 6 Cmd

8480H:bit 9

ON

OFF

C

BV11

MF Input 7 Cmd

8480H:bit 10

ON

OFF

C

BV12

Set Fault Contact Cmd

0009H:bit 6

ENABLE

OFF

C

BV13

RUN-STOP

0020H:bit 0

RUN

OFF

R

BV14

REV-FWD

0020H:bit 1

REV

FWD

R

BV15

READY

0020H:bit 2

READY

OFF

R

BV16

FAULT

0020H:bit 3

FAULTED

OFF

R

BV17

Data Set Error

0020H:bit 4

ERROR

OFF

R

C.6 BACnet Objects Supported

372

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual