General description, Control mode details, 2 general description – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 57

Advertising
background image

1.2 General Description

u

Control Mode Details

Table 1.1

gives an overview of the various features associated with the bypass.

Table 1.1 Control Mode Features

Motor Type

Induction Motors

Comments

Control Mode

V/f

Basic Description

V/f control

Type of Applications

Motor Type

IM

Multi Motor

YES

Motor data unknown

YES

High Speed Accuracy

Control

Characteristics

Speed Control Range

1:40

May fluctuate with characteristics and motor

temperature.

Speed Accuracy

±2 to 3%

Speed deviation when operating at constant speed

may fluctuate with characteristics and motor

temperature.

Speed Response

3 Hz (approx.)

Max. frequency of a speed reference signal that the

drive can follow may fluctuate with characteristics

and motor temperature.

Starting Torque

150% at 3 Hz

Starting torque may fluctuate with characteristics

and motor temperature.

Application-Specific

Auto-Tuning

• Energy Saving Tuning
• Line to line resistance

Automatically adjusts parameter settings that

concern electrical characteristics of the motor.

Speed Search

YES

Bi-directional speed detection of a coasting motor

to restart it without stopping.

Energy-Saving Control

YES

Saves energy by always operating the motor at its

maximum efficiency.

Overexcitation

Deceleration

YES

Provides fast deceleration without using a braking

resistor.

Commercial Power Switching

Selection

YES

When the output frequency matches the power

supply frequency (60 Hz), the PWM switching

operation stops and switches to operation with a

direct commercial power supply connection.

1.2 General Description

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

57