Broadcast messages – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 407

Advertising
background image

Register No.

Contents

8403H

BYP DO-oo Command

Bypass Digital Output Command. These bits allow the digital outputs to be set over a network if

the corresponding digital output function is unused.

Not Used (0/1 for Off/On)

Not Used
Not Used

Not Used

Not Used

Not Used
DO-7

DO-8

X

X

X

X

X

X

X

X

XXXXXXXX

X

X

XXXXXXXX

DO-9

DO-10
Not Used

X

XXXXXX

8404H

Time Set HHMM

Time Set Hours and Minutes. Format is HHMM where HH is hours from 00 to 23 and MM is

minutes from 00 to 59. When new HHMM is set to RTC, the seconds will be set to a value of 0.

8405H

Date Set Year

Date Set Year. Format is YYYY where YYYY is the four digit year from 2000 to 2099.

8406H

Date Set MMDD

Date Set Month and Day. Format is MMDD where MM is month from 01 to 12 and DD is day

from 01 to 31.

8407H

Set RTC

The date and time values in registers 8404H to 8406H are written to the real time clock (RTC) in

the HOA operator connected to the bypass.

0: Do not write values to RTC

1: Write values to RTC

8408H to 843FH

Reserved

8440H

Time HHMM

Time Hours and Minutes. Reads current time. Format is HHMM where HH is hours from 00 to 23

and MM is minutes from 00 to 59. Reads 0x0000 when no RTC option

8441H

Date Year

Date Year. Reads current date. Format is YYYY where YYYY is the year from 0000 to 9999.

Reads 0x0000 when there is no RTC option.

8442H

Date Mo Day MMDD

Date Month and Day. Reads current date. Format is MMDD where MM is month from 01 to12

and DD is day from 01 to 31. Reads 0x0000 when there is no RTC option

8443H to 84FFH

Reserved

8490H

Product Type Code

8491H

Product Type Code

8500H to 87FFH

BYP Parameters and

Monitors

Z1-oo, Z2-oo, Z3-oo, Z4-oo , UB-oo.

Refer to Parameter List on page 307

for Modbus

addresses.

8800H to FFFFH

Reserved

<1> Parameter o1-03, Digital Operator Display Selection, determines the units.
<2> Display is in the following units:

2o0028, 2o0042, and 4o0011 to 4o0027: 0.01 A units
2o0054 to 2o0248 and 4o0034 to 4o0414: 0.1 A units

<3> Communication error contents are saved until the fault is reset.
<4> Set the number of motor poles to parameter E2-04.
<5> Disabled when Z3-12 is set to 0.

u

Broadcast Messages

Data can be written from the master to all slave devices at the same time.
The slave address in a broadcast command message must be set to 00H. All slaves will receive the message, but will not

respond.

D.9 MEMOBUS/Modbus Data Table

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

407

D

MEMOBUS/Modbus Communications