C6: carrier frequency, C7: voltage adjustment – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 317

Advertising
background image

u

C6: Carrier Frequency

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

C6-02

(0224)

Carrier Frequency

Selection

CarrierFreq Sel

1: Fc=4.0 kHz

2: Fc=6.0 kHz

3: Fc=8.0 kHz

4: Fc=10.0 kHz

1: 4.0 kHz

2: 6.0 kHz

3: 8.0 kHz

4: 10.0 kHz

Default:

<1>

Range: 1 to 4

154

C6-03

(0225)

Carrier Frequency

Upper Limit

CarrierFreq Max

Determines the upper and lower limits for the carrier frequency.

Carrier Frequency

E1-04

Max Output

Frequency

Output Frequency

× (C6-05) × K

Output

Frequency

C6-03

C6-04

Default:

<2>

Min.: 4.0 kHz

Max.: 10.0 kHz

C6-04

(0226)

Carrier Frequency

Lower Limit

CarrierFreq Min

Default:

<2>

Min.: 4.0 kHz

Max.: 10.0 kHz

C6-05

(0227)

Carrier Frequency

Proportional Gain

CarrierFreq Gain

Default:

<2>

Min.: 0

Max.: 99

<1> Default setting value is dependent on parameter o2-04, Drive Model Selection.
<2> Default setting value is dependent on parameter C6-02, Carrier Frequency Selection.

u

C7: Voltage Adjustment

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

C7-60

(0B1C)

Output Voltage Limit

Mode Selection

V Out Limit Sel

0: THD Priority

1: Vout Priority

0: Harmonic suppression priority mode

1: High output voltage mode

Default: 1

Range: 0, 1

155

B.4 C: Tuning

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

317

B

Parameter List

Advertising