E.4 APOGEE FLN Point List Summary

This database is for APOGEE FLN Application 2721 and features 97 logical points: 29 Logical Analog Inputs (LAI), 35

Logical Analog Outputs (LAO), 19 Logical Digital Inputs (LDI) and 14 Logical Digital Outputs (LDO). These points configure,

control or monitor the operation of the drive.
Information to consider when referencing this table:
• Points not listed are not used in this application.
• A single value in a column means that the value is the same in English units and in SI units.
• Point numbers that appear in curly brackets, e.g. {03}, can be unbundled at the field panel.

Table E.3 APOGEE FLN Application 2721 Point Number Summary

Point

No.

Point

Type

Point Name

Factory

Default

(SI Units)

Engr. Units

(SI Units)

Slope

(SI Units)

Intercept

(SI Units)

On

Text

Off

Text

Z1000U

Parameter

1

LAO

CTLR

ADDRESS

31

1

0

Z3-02

2

LAO

APPLICATI

ON

1

0

{03}

LAI

FREQ

OUTPUT

0

HZ

0.01

0

U1-02

{04}

LAI

PCT

OUTPUT

0

PCT

0.01

0

{05}

LAI

SPEED

0

RPM

1

0

{06}

LAI

CURRENT

0

AMPS (A)

0.01/0.1

<1>

0

UB-01

{07}

LAI

TORQUE

0

PCT

0.1

0

{08}

LAI

POWER

0

KW

0.01/0.1

<1>

0

U1-08

{09}

LAI

DRIVE

TEMP

0

DEG F / C

1

0

U4-08

{10}

LAI

DRIVE

KWH

0

KWH

0.1

0

U4-10

{11}

LAI

MWH

0

MWH

1

0

U4-11

{12}

LAI

RUN TIME

0

HRS

1

0

U4-01

{13}

LAI

DC BUS

VOLT

0

VOLTS (V)

1

0

U1-07

{14}

LAI

AC OUT

VOLT

0

VOLTS (V)

0.1

0

U1-06

15

LAI

PAR N9.01

0

AMPS (A)

0.01/0.1

<1>

0

n9-01

{16}

LAI

RUN

TIMEX10K

0

10K HR

1

0

U4-01

{17}

LAI

FAULT

CODE

0

1

0

U2-01/

UB-09

{18}

<2>

LDI

MINOR FLT

NO FLT

1

0

FAULT

NO FLT

U1-12 (Bit 6)

{19}

LDI

MAJOR FLT

NO FLT

1

0

FAULT

NO FLT

UB-06 (Bit 2)

20

LAO

OVRD TIME

1

HRS

1

0

{21}

LDI

FWD.REV

FWD

1

0

REV

FWD

U1-12 (Bit 2)

{22}

LDO

CMD

REV.STOP

STOP

1

0

REV

STOP

{23}

LDI

RUN.STOP

STOP

1

0

RUN

STOP

UB-06 (Bit 1)

{24}

LDO

CMD

RUN.STOP

STOP

1

0

FWD

STOP

{25}

LDI

ZERO

SPEED

OFF

1

0

ON

OFF

U1-12 (Bit 1)

{26}

LDI

SPEED

AGREE

NO AGR

1

0

AGREE

NO AGR

U1-12 (Bit 4)

{27}

LDI

DRIVE

READY

NOTRDY

1

0

READY

NOTRDY

U1-12 (Bit 5)