Fault

Name

ov

DC Bus Overvoltage

PF

Input Phase Loss

Uv1

Control Circuit Undervoltage

<1>

Fault

Name

STo

Pull-Out Detection

<1> When L2-01 is set to 0 through 2 (continue operation during momentary power loss).

Use parameters L5-01 to L5-05 to set up automatic fault restart.
Set H2-01, H2-02, or H2-03 to 1E. to output a signal during fault restart.

n

L5-01: Number of Auto Restart Attempts

Sets the number of times that the drive may attempt to restart itself.
Parameter L5-05 determines the method of incrementing the restart counter. When the counter reaches the number set to L5-01,

the operation stops and the fault must be manually cleared and reset.
The restart counter is incremented at each restart attempt, regardless of whether the attempt was successful. When the counter

reaches the number set to L5-01, the operation stops and the fault must be manually cleared and reset.
The number of fault restarts is reset to zero when:
• The drive operates normally for 10 minutes following a fault restart.
• A fault is cleared manually after protective functions are triggered.
• The power supply is cycled.

No.

Name

Setting Range

Default

L5-01

Number of Auto Restart Attempts

0 to 10 Times

0 Times

n

L5-02: Auto Restart Fault Output Operation Selection

Determines if a fault output is triggered (H2-oo = E) when the drive attempts to restart.

No.

Name

Setting Range

Default

L5-02

Auto Restart Fault Output Operation Selection

0, 1

0

Setting 0: No Fault Output

Auto-Restart - Cancel Early
Fault output disabled (L5-02 = 0)

Run command

Fault condition

Fault display

Fault digital output

Output Frequency

(U1-02)

L5-04

Figure 5.45 Auto Restart Cancel Early

Setting 1: Fault Output Is Set

n

L5-03: Time to Continue Making Fault Restarts (enabled only when L5-05 = 0)

Although the drive will continue to execute fault restarts, this parameter will cause a fault if a fault restart cannot occur after

the time set to L5-03 passes.

5.8 L: Protection Functions

188

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual