Z3-08, Z3-09: BACnet Device Object Identifier
These parameters set the Instance Identifier of the BACnet Device Object, where Z3-08 is the least significant word and Z3-09
is the most significant word.
No.
Name
Setting Range
Default
Z3-08
BACnet Device Object Identifier 0
0 to FFFFH
1
Z3-09
BACnet Device Object Identifier 1
0 to 003FH
0
Example 1: Set Device Object Instance Identifier of “1234”.
1234 decimal is equal to 4D2H (hexadecimal).
Set Z3-08 to 4D2H and set Z3-09 to 0.
Example 2: Set Device Object Instance Identifier of “123456”.
123456 decimal is equal to 1E240H.
Set Z3-08 to D687H and set Z3-09 to 12H.