Setting 6: Pump (Secondary) Application

Table 4.12 Pump (Secondary): Parameter Settings

No.

Parameter Name

Default Setting

b1-04

Reverse Operation Selection

1: Reverse operation disabled

C1-01

Acceleration Time 1

20 s

d2-03

Master Speed Reference Lower Limit

20%

L5-01

Number of Auto Restart Attempts

10

L6-01

Stall Prevention Selection during Deceleration

5: UL3 at speed agree (Alarm)

u

Setting 7: Pump with PID Control Application

Table 4.13 Pump with PID Control: Parameter Settings

No.

Parameter Name

Default Setting

b1-04

Reverse Operation Selection

1: Reverse operation disabled

b5-01

PID Function Setting

1: Enabled (PID output becomes output frequency reference)

b5-03

Integral Time Setting (I)

15 s

b5-08

PID Primary Delay Time Constant

10.0 s

b5-13

PID Feedback Low Detection Level

2%

b5-14

PID Feedback Low Detection Time

25 s

b5-15

PID Sleep Function Start Level

72%

b5-16

PID Sleep Delay Time

25.5 s

C1-01

Acceleration Time 1

20 s

d2-03

Master Speed Reference Lower Limit

20%

L5-01

Number of Auto Restart Attempts

10

L6-01

Stall Prevention Selection during Deceleration

5: UL3 at speed agree (Alarm)

4.5 Application Selection

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

125

4

Start-Up Programming & Operation