3.7 External Interlock

Systems that may be affected during drive fault conditions should be interlocked with the drive fault output and ready signal.

u

Annunciation Contact Outputs

Annunciation contacts for customer use are provided at terminal blocks TB1 as indicated in

Table 3.17

. Annunciation contacts

are used to indicate the status of bypass operation. Contacts are rated for 2 Amps, 24 Vdc/120 Vac +/- 15% maximum.

Table 3.17 Annunciation Contact Details

Function

<1>

Name

Terminal Block

Terminals

Type

Motor Run

DO-7

TB1

1-2-3

Form C

Hand Mode

DO-8

TB1

4-5-6

Form C

Auto Mode

DO-9

TB1

7-8-9

Form C

System Fault

DO-10

TB1

10-11-12

Form C

<1> Default settings are shown. Set parameters Z2-23 to Z2-26 to choose other functions.

The function of output relays DO-7 through DO-10 may be reprogrammed via bypass parameters Z2-23 through Z2-26. These

form C dry contact relays are for customer use in annunciation to building automation systems (BAS) or other circuits. Each

contact is rated for 2 amps at 120 Vac.

Refer to Z2-01 to Z2-08: Digital Input 1 to 8 Function Select on page 216

for descriptions of the programmable functions

of annunciation contacts.

u

Building Automation System Run/Stop Circuit

DI-1 (TB2-1 by default setting in Z2-01) is available to connect the normally open (N.O.) Run/Stop contact from a BAS or

other remote controller for auto mode control.
These terminals must have contact closure for the motor to run in AUTO mode.

u

Safety Interlock Circuit

DI-2 (TB2-2 by default setting in Z2-02) is provided to connect safety devices in a normally-closed series circuit, such as:

freeze up thermostats, smoke/fire sensors, high pressure limits, temperature limits or vibration detectors.
The HOA keypad will display the status “Safety Open”, and trigger a Safety Open fault if a N.C. safety circuit is not closed

between DI-2 and IG24 (TB2-10) on PCB A2 at power-up with a Run command in HAND or AUTO mode. An open circuit

between DI-2 and IG24 will prevent bypass operation.
Take one of the following steps to ensure proper operation prior to startup:

1.

Install a N.C. safety circuit between DI-2 and IG24 on PCB A2.

2.

Install a jumper between DI-2 and IG24 (on PCB A2. A normally-closed safety circuit may also be used in place of

this jumper.

u

Building Automation System Interlock Circuit (Drive and Bypass Enable Input)

The HOA keypad will display the status “INTRLOCK OPN” and possibly a “BAS Ilock-open” alarm or “BAS Ilock TO”

fault if a N.C. safety circuit is not closed between DI-3 (TB2-3 by default setting of Z2-03) and IG24 on PCB A2 at power-

up with a Run command in HAND or AUTO mode. An open circuit between TB2-3 and IG24 (TB2-10) will prevent bypass

operation.
Take one of the following steps to ensure proper operation prior to startup:

1.

Install a N.C. BAS Interlock Circuit/Damper Interlock between DI-3 and IG24 on PCB A2.

2.

Install a jumper between DI-3 and IG24 on PCB A2. A normally-closed BAS interlock may also be used in place of

this jumper.

3.7 External Interlock

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual