A.1 Power Ratings

u

Three-Phase 208 Vac Models D024 to D211

Table A.1 Power Ratings (Three-Phase 208 V)

Item

Specification

Bypass Model Z1D1

D024

D030

D046

D059

D074

D088

D114

D143

D169

D211

Maximum

Applicable

Motor

Capacity

<1>

HP

7.5

10

15

20

25

30

40

50

60

75

Input

Input Current (A)

<2>

23.3

29.5

43.6

55.8

70

82.1

105.2

132.4

156.4

194.7

Rated Voltage

Rated Frequency

Three-phase 208 Vac 50/60 Hz

Allowable Voltage Fluctuation

-15 to 10%

Allowable Frequency Fluctuation

±5%

Output

Rated Output Current (A)

24.2

<3>

30.8

<3>

16.2

<3>

59.4

<3>

74.8

<3>

88.0

<3>

114.0

<3>

143.0

<3>

169.0

<3>

211.0

<3>

Overload Tolerance

120% of rated output current for 60 s

150% peak

Carrier Frequency

User adjustable between 4 and 10 kHz

(Maximum Frequency varies with Rated Output Capacity)

Maximum Output Voltage (V)

Three-phase 208 Vac

Maximum Output Frequency (Hz)

400 Hz

EMC

Filter

(IEC/EN 61800-3 Category 2)

Built-in

<1> The motor capacity (HP) refers to an NEC Table 430.250 208 V motor. The rated output current of the drive output amps should be equal to or

greater than the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.

<2> Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring

connections, and power supply impedance.

<3> Carrier frequency is set to 4 kHz. Current derating is required to raise the carrier frequency.

A.1 Power Ratings

300

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual