N: special adjustment, N1: hunting prevention, N3: overexcitation braking – Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 334: B.10 n: special adjustment

B.10 n: Special Adjustment
The n parameters adjust more advanced performance characteristics such as Hunting Prevention, speed feedback detection,
High Slip Braking, and Online Tuning for motor line-to-line resistance.
u
n1: Hunting Prevention
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
n1-01
(0580)
Hunting Prevention
Selection
Hunt Prev Select
0: Disabled
1: Enabled
0: Disabled
1: Enabled
Default: 1
Range: 0, 1
n1-02
(0581)
Hunting Prevention
Gain Setting
Hunt Prev Gain
If the motor vibrates while lightly loaded, increase the gain by
0.1 until vibration ceases. If the motor stalls, decrease the gain
by 0.1 until the stalling ceases.
Default: 1.00
Min.: 0.00
Max.: 2.50
u
n3: Overexcitation Braking
No.
(Addr.
Hex)
Name
LCD Display
Description
Values
Page
n3-13
(0531)
Overexcitation
Deceleration Gain
Hflux Brake Gain
Sets the gain applied to the V/f pattern during Overexcitation
Deceleration (L3-04 = 4).
Default: 1.10
Min.: 1.00
Max.: 2.00
B.10 n: Special Adjustment
334
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual