Figure 1.6 – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 64

Advertising
background image

B

G

E

F

M

A

D

A

B

C

D

C

C

G

C

L

H

I

J

K

A – Main input disconnect
B – Motor overload
C – Bypass contactor
D – Soft starter option PW
E – Air filter
F – Enclosure cooling fan
G – 120 V control transformer

H – Terminal TB1
I – Terminal TB2
J – Terminal TB3
K – Communications port CN2
L – Option card connector CN5
M – Ground terminal

Figure 1.6 Interior View of Bypass Unit

n

Circuit Breaker (100 kAIC)

Electrically located on the input power side of the bypass, the door mounted circuit breaker provides a means of disconnecting

the bypass from line power for equipment maintenance. The circuit breaker must be in the OFF position to open the bypass

enclosure door. When opened, the handle can be locked in the OFF position using a padlock.
Branch short circuit protection for the bypass must be supplied by the customer.

n

Contactors

The bypass is a 2-contactor or 3-contactor bypass circuit employing IEC rated contactors in an electrically interlocked

arrangement to allow mutually exclusive operation in Drive or Bypass modes.
The control logic and “soft start” characteristic of the drive limit the drive input and output contactors to motor FLA current

or less. For this reason, the drive output contactor has a lower current rating than the bypass contactor. The bypass contactor

is exposed to motor inrush current (LRA) when starting the motor across-the-line and therefore requires a higher current rating.

1.5 Bypass Component Descriptions

64

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

Advertising