Figure 5.58, Z1-24: contactor open delay time – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 212

Advertising
background image

VFD RUN COMMAND

VFD OUTPUT FREQUENCY

DAMPER ACTUATOR OUTPUT

BAS INTERLOCK INPUT

t1

t2

t3

VFD FREQUENCY REFERENCE

Parameter Settings:
Z1-12 Run Delay Time = 0.0 sec
Z1-13 Pre Int Run Sel = 1 (Enable)
Z1-14 Run Delay Fref = 30.0 Hz
Z1-15 Interlck Wait Tm = 0.0 sec (Never Time Out)

Z1-14 Run Delay Fref

t4

Figure 5.57 Run Delay with Preset Speed Example: Preset Speed

Figure 5.58 Run Delay with Preset Speed Example: Preset Speed with Run Delay

n

Z1-24: Contactor Open Delay Time

Sets the time to delay after commanding the drive output contactor K2 or bypass contactor K3 or 2-Motor AND/OR contactors

K4 and K5 to open to allow the contacts to open.

No.

Name

Setting Range

Default

Z1-24

Contactor Open Delay Time

0.0 to 5.0 s

0.2 s

5.14 Z: Bypass Parameters

212

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual