B2: dc injection braking and short circuit braking – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 135

Advertising
background image

Setting 0: Reverse Enabled

Possible to operate the motor in both forward and reverse directions.

Setting 1: Reverse Disabled

Drive disregards a Reverse run command or a negative frequency reference.

n

b1-24: Commercial Power Operation Switching Selection

When the output frequency matches the power supply frequency (60 Hz), the PWM switching operation stops and switches

to operation with a direct commercial power supply connection.

Note:

1. Switching can be enabled when an inductive motor is being driven.
2. Current value may change when a switch is made.
3. Verify that the induction motor can be driven with the commercial power supply (e.g., the rated voltage and rated speed) prior to enabling

the commercial power switching selection.

No.

Parameter Name

Setting Range

Default

b1-24

Commercial Power Switching Selection

0, 1

0

Setting 0: Disabled

A voltage will be output with PWM switching operation regardless of the output frequency.

Setting 1: Enabled

When the deviation between the output frequency and the power supply frequency is less than or equal to the commercial

power switching output frequency coincidence level (b1-26), the PWM switching operation stops and switches to operation

with a direct commercial power supply connection.
Operation with a direct commercial power supply continues until the deviation between the output frequency and the power

supply frequency is greater than or equal to the commercial power switching output frequency coincidence/non-coincidence

level (b1-25 + b1-26).

n

b1-25/b1-26: Commercial Power Switching Output Frequency Coincidence Level/Non-

coincidence Level

These parameters set the value in 0.1 Hz increments at which commercial power supply switching selection is enabled and

disabled.
When the deviation between the output frequency and the power supply frequency becomes equal to or less than the setting

values of b1-25 + b1-26, an output frequency coincidence condition exists. The drive will operate in commercial power

switching mode. If the drive will not switch to commercial power supply switching mode, set b1-26.
When the deviation between the output frequency and the power supply frequency becomes equal to or greater than the setting

value of b1-25, the drive will operate in PWM switching mode. If commercial power switching mode and PWM switching

mode are repeated frequently, increase the setting value of b1-25.

Note:

The drive will not switch to commercial power switching mode when L3-06, Stall Prevention Level during Run, is exceeded and L3-05,

Stall Prevention Selection during Run, is enabled.

No.

Parameter Name

Setting Range

Default

b1-25

Commercial Power Supply Operation Switching Level

0.4 to 6.0 Hz

1.0 Hz

b1-26

Commercial Power Supply Operation Switching Level

0.0 to 3.0 Hz

0.2 Hz

u

b2: DC Injection Braking and Short Circuit Braking

These parameters determine operation of the DC Injection Braking, Zero Speed Control, and Short Circuit Braking features.

n

b2-01: DC Injection Braking Start Frequency

Active when “Ramp to Stop” is selected as the stopping method (b1-03 = 0).

No.

Name

Setting Range

Default

b2-01

DC Injection Braking Start Frequency

0.0 to 10.0 Hz

0.5 Hz

b2-01 sets the starting frequency for DC Injection Braking at Stop. When the output frequency falls below the setting of b2-01,

DC Injection Braking is enabled for the time set in parameter b2-04.

5.2 b: Application

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

135

5

Programming