5 e: motor parameters, Table 5.11 high starting torque, settings 8 to b, Table 5.12 rated output operation, settings c to f – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 160

Advertising
background image

Predefined V/f Patterns for Models B011 and B014

Table 5.9 Constant Torque Characteristics, Settings 0 to 3

Setting = 0

50 Hz

Setting = 1

60 Hz

Setting = 2

60 Hz

Setting = 3

72 Hz

0

18

400

1.3 2.5

50

30

V

oltage (V)

Frequency (Hz)

0

18

30

400

1.5 3

60

V

oltage (V)

Frequency (Hz)

0

18

30

400

1.5 3

60

50

V

oltage (V)

Frequency (Hz)

0

18

30

400

1.5 3

72

60

V

oltage (V)

Frequency (Hz)

Table 5.10 Derated Torque Characteristics, Settings 4 to 7

Setting = 4

50 Hz

Setting = 5

50 Hz

Setting = 6

60 Hz

Setting = 7

60 Hz

0

16

400

1.3

25

50

70

V

oltage (V)

Frequency (Hz)

0

18

400

1.3

25

50

100

V

oltage (V)

Frequency (Hz)

0

16

400

1.5

30

60

70

V

oltage (V)

Frequency (Hz)

0

18

400

1.5

30

60

100

V

oltage (V)

Frequency (Hz)

Table 5.11 High Starting Torque, Settings 8 to B

Setting = 8

50 Hz

Setting = 9

50 Hz

Setting = A

60 Hz

Setting = B

60 Hz

0

22

400

1.3 2.5

50

38

V

oltage (V)

Frequency (Hz)

0

26

400

1.3 2.5

50

48

V

oltage (V)

Frequency (Hz)

0

22

400

1.5 3

60

38

V

oltage (V)

Frequency (Hz)

0

30

400

1.5 3

60

48

V

oltage (V)

Frequency (Hz)

Table 5.12 Rated Output Operation, Settings C to F

Setting = C

90 Hz

Setting = D

120 Hz

Setting = E

180 Hz

Setting = F

60 Hz

0

18

30

400

1.5 3

90

60

V

oltage (V)

Frequency (Hz)

0

18

30

400

1.5 3

120

60

V

oltage (V)

Frequency (Hz)

0

18

30

400

1.5 3

180

60

V

oltage (V)

Frequency (Hz)

0

18

30

400

1.5 3

60

V

oltage (V)

Frequency (Hz)

5.5 E: Motor Parameters

160

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual