HOA Keypad Display

Error Name

H2-oo is set to 38 (Drive Enabled) and H1-oo

is not set to 6A (Drive Enable)

Correct the settings for the multi-function input terminal parameters.

HOA Keypad Display

Error Name

oPE04

Initialization Required

Cause

Possible Solutions

The drive, control board, or terminal board have

been replaced and the parameter settings between

the control board and the terminal board no longer

match.

Set A1-03 to 5550 to load the parameter settings stored in the terminal board to the drive. Initialize

parameters after drive replacement by setting A1-03 to 2220 or 3330.

HOA Keypad Display

Error Name

oPE05

Run Command/Frequency Reference Source Selection Error

Cause

Possible Solutions

Frequency reference is assigned to an option card

(b1-01 = 3) and an input option card is not

connected to the drive

Reconnect the input option card to the drive.

The Run command is assigned to an option card

(b1-02 = 3) and an input option card is not

connected to the drive

HOA Keypad Display

Error Name

oPE07

Multi-Function Analog Input Selection Error
A contradictory setting is assigned to multi-function analog inputs H3-02, H3-10, and H3-06 and PID

functions conflict.

Cause

Possible Solutions

At least two analog input terminals are set to the

same function

Change the settings to H3-02, H3-10, and H3-06 so that functions no longer conflict.

Note:

Both 0 (Frequency Reference Bias) and F (Not Used) can be set to H3-02, H3-10, and

H3-06 simultaneously.

The following simultaneous contradictory

settings:

H3-02, H3-10, or H3-06 = C (PID Target Value)

while

b5-18 = 1 (enables b5-19 as the target PID value)

Disable one of the PID selections.

HOA Keypad Display

Error Name

oPE08

Parameter Selection Error

Cause

Possible Solutions

A function has been set that cannot be used in the

control mode.

The bypass only supports V/f control mode. Limit selections to those with V/f mode compatibility.

Note:

Use U1-18 to find parameters that are set outside the specified setting range. When multiple errors occur simultaneously, other errors are

given precedence over oPE08.

HOA Keypad Display

Error Name

oPE09

PID Control Selection Fault
PID control function selection is incorrect. Requires that PID control is enabled (b5-01 = 1 or 3).

Cause

Possible Solutions

The following simultaneous contradictory settings

have occurred:
• b5-15 is not set to 0.0 (PID Sleep Function

Operation Level)

• The stopping method is set to either DC

Injection Braking or coast to stop with a timer

(b1-03 = 2 or 3)

• Set b5-15 to a value other than 0.0.
• Set the stopping method to coast to stop or ramp to stop (b1-03 = 0 or 1).

b5-01 is set to 1, enabling PID control, but the

lower limit for the frequency reference (d2-02) is

not set to 0 while reverse output is enabled

(b5-11 = 1)

Correct the parameter settings.

b5-01 is set to 3, enabling PID control, but the

lower limit for the frequency reference (d2-01) is

not 0

Correct the parameter settings.

6.6 Operator Programming Errors

260