For a list of functions and descriptions – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 178

Advertising
background image

Setting 6: A2 and A3 Only Enabled

Setting 7: All Analog Input Terminals Enabled

n

H3-16 to H3-18: Terminal A1/A2/A3 Offset

Set the offset level of the selected input value to terminals A1, A2, or A3 that is equal to 0 Vdc input. These parameters rarely

require adjustment.

No.

Name

Setting Range

Default

H3-16

Terminal A1 Offset

-500 to 500

0

H3-17

Terminal A2 Offset

-500 to 500

0

H3-18

Terminal A3 Offset

-500 to 500

0

n

Multi-Function Analog Input Terminal Settings

See

Table 5.23

for information on how H3-02 and H3-10 determine functions for terminals A1, A2, and A3.

Note:

The scaling of all input functions depends on the gain and bias settings for the analog inputs. Set these to appropriate values when selecting

and adjusting analog input functions.

Table 5.23 Multi-Function Analog Input Terminal Settings

Setting

Function

Page

0

Frequency Bias

178

1

Frequency Gain

178

2

Auxiliary Frequency Reference 1

178

3

Auxiliary Frequency Reference 2

178

4

Output Voltage Bias

178

5

Accel/Decel Time Gain

179

6

DC Injection Braking Current

179

7

Overtorque/Undertorque Detection Level

179

8

Stall Prevention Level During Run

179

9

Output Frequency Lower Limit Level

179

Setting

Function

Page

B

PID Feedback

179

C

PID Setpoint

180

D

Frequency Bias

180

E

Motor Temperature (PTC Input)

180

F

Through Mode

180

16

Differential PID Feedback

180

1F

HAND Reference

180

25

Secondary PI Setpoint

180

26

Secondary PI Feedback

180

Setting 0: Frequency Bias

The input value of an analog input set to this function will be added to the analog frequency reference value. When the frequency

reference is supplied by a different source other than the analog inputs, this function will have no effect. Use this setting also

when only one of the analog inputs is used to supply the frequency reference.
By default, analog inputs A1 and A2 are set for this function. Simultaneously using A1 and A2 increases the frequency reference

by the total of all inputs.
Example: If the analog frequency reference from analog input terminal A1 is 50% and a bias of 20% is applied by analog input

terminal A2, the resulting frequency reference will be 70% of the maximum output frequency.

Setting 1: Frequency Gain

The input value of an analog input set to this function will be multiplied with the analog frequency reference value.
Example: If the analog frequency reference from analog input terminal A1 is 80% and a gain of 50% is applied from analog

input terminal A2, the resulting frequency reference will be 40% of the maximum output frequency.

Setting 2: Auxiliary Reference 1

Sets the auxiliary frequency reference 1 when multi-step speed operation is selected.

Refer to Multi-Step Speed Selection on

page 156

for details.

Setting 3: Auxiliary Reference 2

Sets the auxiliary frequency reference 2 when multi-step speed operation is selected.

Refer to Multi-Step Speed Selection on

page 156

for details.

Setting 4: Output Voltage Bias

Voltage bias boosts the output voltage of the V/f curve as a percentage of the maximum output voltage (E1-05). Available

only when using V/f Control.

5.7 H: Terminal Functions

178

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

Advertising