Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 257

Advertising
background image

HOA Keypad Display

Minor Fault Name

Motor has overheated

• Check the load size, accel/decel times, and cycle times.
• Decrease the load.
• Increase accel and decel times (C1-01 and C1-02).
• Adjust the preset V/f pattern (E1-04 through E1-10). This involves reducing E1-08 and E1-10.

Note:

Refrain from lowering E1-08 and E1-10 excessively to prevent a reduction in load

tolerance at low speeds.

• Check the motor-rated current.
• Enter motor-rated current on motor nameplate (E2-01).
• Ensure the motor cooling system is operating normally.
• Repair or replace the motor cooling system.

HOA Keypad Display

Minor Fault Name

oL3

Overtorque 1
Drive output current was greater than L6-02 for longer than the time set to L6-03.

Cause

Possible Solutions

Inappropriate parameter settings

Check parameters L6-02 and L6-03.

There is a fault on the machine side (e.g., the

machine is locked up)

• Check the status of the machine.
• Remove the cause of the fault.

HOA Keypad Display

Minor Fault Name

ov

Control Circuit Overvoltage
Voltage in the control circuit has exceeded the trip point.
• For 200 V class drives: approximately 450 V
• For 400 V class drives: approximately 900 V

Cause

Possible Solution

Surge voltage present in the drive input power.

Voltage surge can result from a thyristor convertor and a phase advancing capacitor operating on the

same drive input power system.

Drive input power voltage is too high.

• Check the voltage.
• Lower drive input power voltage within the limits listed in the specifications.

The capacity of the input power supply is too small. Use a power supply that has at least twice the input capacity of the drive.
The input power supply repeatedly turned on and

off over a short period of time.

Implement countermeasures so that chattering does not occur for the input power supply.

An I/O terminal is loose.

Check the tightening torque of the I/O terminals.

There is a phase loss or an imbalance in the

interphase voltages of the input power supply.

Check the status of the input power supply and eliminate phase losses and imbalance.

HOA Keypad Display

Minor Fault Name

PASS

MEMOBUS/Modbus Comm. Test Mode Complete

Cause

Possible Solutions

MEMOBUS/Modbus test has finished normally

This verifies that the test was successful.

HOA Keypad Display

Minor Fault Name

SAFE

Customer Safety
Customer Safeties multi-function input is open. This alarm has display priority over the Interlock

Open (inTLK).

Cause

Possible Solutions

External contact from customer wiring is open.

Check the cause of the open safety.

HOA Keypad Display

Minor Fault Name

SE

MEMOBUS/Modbus Communication Test Mode Error

Note:

This alarm will not trigger a multi-function output terminal that is set for alarm output

(H2-oo = 10).

Cause

Possible Solutions

A digital input set to 67H (MEMOBUS/Modbus

test) was closed while the drive was running

Stop the drive and run the test again.

6.5 Alarm Detection

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

257

6

Diagnostics & Troubleshooting