B.16 Defaults by Drive Model

The following tables show parameters and default settings that change with the drive model selection (o2-04).

Table B.3 200 V Class Drives Default Settings by Drive Model Selection

No.

Name

Unit

Default Settings

Drive Model

2o0028

2o0042

2o0054

2o0068

o2-04

Drive Model Selection

Hex.

6A

6B

6D

6E

b3-04

V/f Gain during Speed Search

%

100

100

100

100

b3-06

Output Current 1 during Speed Search

0.5

0.5

0.5

0.5

b3-08

Current Control Gain during Speed Search

(Speed Estimation Type)

0.5

0.5

0.5

0.5

C6-02

Carrier Frequency Selection

1

1

1

1

E2-01

Motor Rated Current

A

26.6

39.7

53

65.8

E2-03

Motor No-Load Current

A

8

11.2

15.2

15.7

L2-02

Momentary Power Loss Ride-Thru Time

s

0.8

0.9

1

1

L2-03

Momentary Power Loss Minimum Baseblock

Time

s

0.3

0.3

0.6

0.6

L8-02

Overheat Alarm Level

°C

130

130

130

130

L8-38

Carrier Frequency Reduction Selection

1

1

1

1

Table B.4 200 V Class Drives Default Settings by Drive Model Selection

No.

Name

Unit

Default Settings

Drive Model

2o0081

2o0104

2o0130

2o0154

2o0192

2o0248

o2-04

Drive Model Selection

Hex.

6F

70

72

73

74

75

b3-04

V/f Gain during Speed Search

%

100

80

80

80

80

80

b3-06

Output Current 1 during Speed Search

0.5

0.5

0.5

0.5

0.5

0.7

b3-08

Current Control Gain during Speed

Search

(Speed Estimation Type)

0.5

0.5

0.5

0.5

0.5

0.5

C6-02

Carrier Frequency Selection

1

1

1

1

1

1

E2-01

Motor Rated Current

A

77.2

105

131

160

190

260

E2-03

Motor No-Load Current

A

18.5

21.9

38.2

44

45.6

72

L2-02

Momentary Power Loss Ride-Thru

Time

s

1

1.1

1.1

1.2

1.3

1.5

L2-03

Momentary Power Loss Minimum

Baseblock Time

s

0.6

0.6

0.6

1

1

1

L8-02

Overheat Alarm Level

°C

130

130

130

130

130

130

L8-38

Carrier Frequency Reduction

Selection

1

1

1

1

1

1

Table B.5 400 V Class Drives Default Settings by Drive Model Selection

No.

Name

Unit

Default Settings

Drive Model

4o0011

4o0014

4o0021

4o0027

o2-04

Drive Model Selection

Hex.

95

97

99

9A

b3-04

V/f Gain during Speed Search

%

100

100

100

100

b3-06

Output Current 1 during Speed Search

0.5

0.5

0.5

0.5

b3-08

Current Control Gain during Speed Search

(Speed Estimation Type)

0.5

0.5

0.5

0.5

C6-02

Carrier Frequency Selection

1

1

1

1

E2-01

Motor Rated Current

A

7

9.8

13.3

19.9

E2-03

Motor No-Load Current

A

2.3

2.6

4

5.6

L2-02

Momentary Power Loss Ride-Thru Time

s

0.6

0.7

0.8

0.9

L2-03

Momentary Power Loss Minimum Baseblock

Time

s

0.3

0.3

0.3

0.3

L8-02

Overheat Alarm Level

°C

130

130

130

130

L8-38

Carrier Frequency Reduction Selection

1

1

1

1

B.16 Defaults by Drive Model

358