HOA Keypad Display

Error Name

oPE10

V/f Data Setting Error
One of the following setting errors has occurred:

E1-04 ≥ E1-06

E1-06 ≥ E1-07

E1-07 ≥ E1-09

or E1-09 ≥ E1-11

Cause

Possible Solutions

V/f pattern setting error

Correct the settings for E1-04, E1-06, E1-07, E1-09, and E1-11.

HOA Keypad Display

Error Name

oPE11

Carrier Frequency Setting Error
Correct the setting for the carrier frequency.

Cause

Possible Solutions

The following simultaneous contradictory settings

have occurred: C6-05 > 6 and C6-04 > C6-03

(carrier frequency lower limit is greater than the

upper limit)

If C6-05 ≤ 6, the drive operates at C6-03

Correct the parameter settings.

The upper and lower limits between C6-02 and

C6-05 are contradictory

HOA Keypad Display

Error Name

oPE16

Energy Saving Constants Error

Cause

Possible Solutions

The following contradictory settings are true:

A1-02 = 0, S1-01 =1, and b8-01 = 1

Correct the parameter settings.

HOA Keypad Display

Error Name

oPE27

BP Program Error
Bypass mode is not correctly configured.

Cause

Possible Solutions

If digital inputs A4, A5, or A7 or digital outputs

A4 or A5 are programmed, then all must be

programmed

Correct the parameter settings.

Digital inputs A4, A5, or A7 and digital outputs A4

or A5 are programmed and one of the following

conditions is true:
• H1-0o = 0 (3-Wire Sequence)
• L5-01 > 0 and S4-01 = 1 (Auto Transfer of Fault)

HOA Keypad Display

Error Name

oPE28

Sequence Timer Error
One or more of the sequence timers is not set in the correct order.

Cause

Possible Solutions

One of the following contradictory settings is true:
• S2-01 > S2-02
• S2-06 > S2-07
• S2-11 > S2-12
• S2-16 > S2-17

Correct the parameter settings.

HOA Keypad Display

Error Name

oPE30

Incorrect Input Voltage Adjustment
The input voltage offset adjustment has not been performed.

Cause

Possible Solutions

• o2-04, Drive Model Selection, setting changed.
• ERPROM failed for the input voltage offset.

Contact Yaskawa or your nearest sales representative for information on clearing the error.

6.6 Operator Programming Errors

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

261

6

Diagnostics & Troubleshooting

Advertising