Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 218

Advertising
background image

Setting 31: HAND Select

When this is selected, the HAND function command will come from a digital input while the HAND key on the HOA operator

will be ignored. If both HAND and AUTO functions are configured to come from digital inputs, the lack of both of these

inputs being active will put the HOA function into the OFF state. The OFF key on the HOA operator will always place the

HOA function to the OFF state.

Setting 32: AUTO Select

When this is selected, the AUTO function command will come from a digital input while the AUTO key on the HOA operator

will be ignored. If both HAND and AUTO functions are configured to come from digital inputs, the lack of both of these

inputs being active will put the HOA function into the OFF state. The OFF key on the HOA operator will always place the

HOA function to the OFF state

Setting 33: DRIVE/BYPASS Select

When this is selected, the DRIVE/BYPASS select function command will come from a digital input while the DRV/BYP key

on the HOA operator will be ignored.
Input OFF: Drive Mode is selected.
Input ON: Bypass Mode is selected.

Setting 34: Fault Reset

Resets any faults that are present.

Setting 35: External Fault (EF0)

Issues external fault EF0 to the drive from the bypass. Use parameter Z1-30 to modify the fault delay time.

Setting 36: External Fault (EFB)

Triggers external EFB on the bypass.

Setting 37: Run Reverse (AUTO Mode)

Starts and stops the bypass in reverse when Z1-08 is set to 1.

n

Z2-09 to Z2-16: Digital Input 1 to 8 Invert Select

No.

Name

Setting Range

Default

Z2-09

Digital Input 1 Invert Select

0, 1

0

Z2-10

Digital Input 2 Invert Select

0, 1

0

Z2-11

Digital Input 3 Invert Select

0, 1

0

Z2-12

Digital Input 4 Invert Select

0, 1

0

Z2-13

Digital Input 5 Invert Select

0, 1

0

Z2-14

Digital Input 6 Invert Select

0, 1

0

Z2-15

Digital Input 7 Invert Select

0, 1

0

Z2-16

Digital Input 8 Invert Select

0, 1

0

n

Bypass Digital Input Invert Settings

Table 5.30 Bypass Digital Input Invert Settings

Setting

Function

Page

0

Normal

218

Setting

Function

Page

1

Inverted

218

Setting 0: Normal

Lack of input signal = OFF

Setting 1: Inverted

Lack of input signal = ON

5.14 Z: Bypass Parameters

218

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual