6.5 Alarm Detection

u

Alarm Codes, Causes, and Possible Solutions

Alarms are drive protection functions that do not necessarily cause the drive to stop. Once the cause of an alarm is removed,

the drive will return to the same status is was before the alarm occurred.
When an alarm has been triggered, the ALM light on the HOA keypad display blinks and the alarm code display flashes. If a

multi-function output is set for an alarm (H2-oo = 10), that output terminal will be triggered.

Note:

If a multi-function output is set to close when an alarm occurs (H2-oo = 10), it will also close when maintenance periods are reached,

triggering alarms LT-1 through LT-3 (triggered only if H2-oo = 2F).

Table 6.9 Alarm Codes, Causes, and Possible Solutions

HOA Keypad Display

Minor Fault Name

AEr

Station Address Setting Error (CC-Link, CANopen, MECHATROLINK)
Option card node address is outside of the acceptable setting range.

Cause

Possible Solutions

Station number is set outside the possible setting

range.

Set parameters to the proper values when using options.

HOA Keypad Display

Fault Name

AL02

BAS Interlock Open

Cause

Possible Solution

The digital input set to BAS interlock is open

Check to see if the damper is functioning properly. The damper may be in the process of opening and

the end switch may not have closed.

HOA Keypad Display

Fault Name

AL03

Smoke Purge in Bypass

Note:

Also referred to as “Fireman's Override” (Bypass).

Cause

Possible Solution

Smoke Purge Bypass input is activated

This is typically an intentional emergency run state. Check the Z2-oo digital input settings to

determine which is set to 25, then check to the physical digital input terminal DI-oo to determine

why it is closed.

HOA Keypad Display

Fault Name

AL04

Smoke Purge in Drive

Note:

Also referred to as “Fireman's Override” (Drive).

Cause

Possible Solution

Smoke Purge Drive input is activated

This is typically an intentional emergency run state. Check the digital input settings (Z2-oo) to

determine which is set to 25. Then check to the physical digital input terminal DI-oo to determine

why it is closed.

HOA Keypad Display

Fault Name

AL13

Loss of Load

Cause

Possible Solution

The conditions were such that it appears that the

motor has been disconnected from the load.

Replace the belt or coupling between the motor and the load. In the event of a false detection, review

parameters Z1-27 to Z1-32 and set them to more appropriate values.

HOA Keypad Display

Fault Name

AL14

Serial Comm Alarm

Cause

Possible Solution

Faulty communication wiring or an existing short

circuit.

• Check for faulty serial communication wiring
• Correct the wiring
• Check for disconnected cables and short circuits and repair as needed.

6.5 Alarm Detection

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

251

6