Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 399

Advertising
background image

Register No.

Contents

00ACH

Motor Speed (U1-05)

r/min units

<4>

00ADH

0.01% units

00AEH to 00B1H

Reserved

00B2H

Option Code Connected to CN5-B

00B3H

Option Code Connected to CN5-C

00B4H

Reserved

00B5H

Frequency Reference After

Soft-starter (U1-16)

r/min units

<4>

00B6H

0.01% units

00B7H

Frequency Reference

r/min

<4>

00B8H

0.01% units

00B9H to 00BEH

Reserved

00BFH

Lists the last two digits of operation error code oPEoo.

00C0H

Fault Contents 3
bit 1

Control Circuit Undervoltage Fault (Uv1)

bit 2

Control Power Supply Undervoltage Fault (Uv2)

bit 3

Undervoltage 3 (Soft-Charge Bypass Circuit Fault) (Uv3)

bit 4

Reserved

bit 5

Ground Fault (GF)

bit 6

Overcurrent (oC)

bit 7

Control Circuit Overvoltage (ov)

bit 8

Heatsink Overheat (oH)

bit 9

Overheat 1 (oH1)

bit A

Motor Overload (oL1)

bit B

Overload (oL2)

bit C

Overtorque Detection 1 (oL3)

bit D

Overtorque Detection 2 (oL4)

bit E, F

Reserved

00C1H

Fault Contents 4
bit 0

External Fault at input terminal S3 (EF3)

bit 1

External Fault at input terminal S4 (EF4)

bit 2

External Fault at input terminal S5 (EF5)

bit 3

External Fault at input terminal S6 (EF6)

bit 4

External Fault at input terminal S7 (EF7)

bit 5

External Fault at input terminal S8 (EF8)

bit 6

Fan Fault (FAn)

bit 7

Overspeed (os)

bit 8

Excessive Speed Deviation (dEv)

bit 9

PG Disconnect (PGo)

bit A

Reserved

bit B

Output Phase Loss (LF)

bit C

Motor Overheat (PTC input) (oH3)

bit D

External Digital Operator Connection Fault (oPr)

bit E

EEPROM Write Error (Err)

bit F

Motor Overheat Fault (PTC input) (oH4)

D.9 MEMOBUS/Modbus Data Table

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

399

D

MEMOBUS/Modbus Communications