Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 356

Advertising
background image

No.

(Addr.

Hex)

Name

Description

Values

Page

Z4-06

(8705)

Subnet Mask 2

Sets the second most significant octet of network static subnet mask.

Default: 255

Range: 0 to 255

223

Z4-07

(8706)

Subnet Mask 3

Sets the third most significant octet of network static subnet mask.

Default: 255

Range: 0 to 255

223

Z4-08

(8707)

Subnet Mask 4

Sets the fourth most significant octet of network static subnet mask.

Default: 0

Range: 0 to 255

223

Z4-09

(8708)

Gateway IP Address 1

Sets the most significant octet of network gateway address.

Default: 192

Range: 0 to 255

223

Z4-10

(8709)

Gateway IP Address 2

Sets the second most significant octet of network gateway address.

Default: 168

Range: 0 to 255

223

Z4-11

(870A)

Gateway IP Address 3

Sets the third most significant octet of network gateway address.

Default: 1

Range: 0 to 255

223

Z4-12

(870B)

Gateway IP Address 4

Sets the fourth most significant octet of network gateway address.

Default: 1

Range: 0 to 255

223

Z4-13

(870C)

IP Address Mode Select

0: User-Defined (Static IP)

1: BOOTP

2: DHCP

Default: 2

Range: 0 to 2

223

Z4-14

(870D)

Duplex Select

0: Forced Half Duplex

1: Auto Negotiate Duplex Mode and Communication Speed

2: Forced Full Duplex

Default: 1

Range: 0 to 2

223

Z4-15

(870E)

Speed Mode Setting

10: 10 Mbps

100: 100 Mbps

Default: 10

Range: 10, 100

223

Z4-16

(870F)

Communication Loss

Timeout

Control connection timeout value for detection of communication loss.

Default: 0 s

Min.: 0

Max.: 300

224

Z4-17

(8710)

Ethernet Speed Scale

AC/DC Drive Object, Instance 1, Attribute 22

Default: 0

Min.: -15

Max.: 15

224

Z4-18

(8711)

Ethernet Current Scale

AC/DC Drive Object, Instance 1, Attribute 23

Default: 0

Min.: -15

Max.: 15

224

Z4-19

(8712)

Ethernet Torque Scale

AC/DC Drive Object, Instance 1, Attribute 24

Default: 0

Min.: -15

Max.: 15

224

Z4-20

(8713)

Ethernet Power Scale

AC/DC Drive Object, Instance 1, Attribute 26

Default: 0

Min.: -15

Max.: 15

224

Z4-21

(8714)

Ethernet Voltage Scale

AC/DC Drive Object, Instance 1, Attribute 27

Default: 0

Min.: -15

Max.: 15

224

Z4-22

(8715)

Ethernet Time Scale

AC/DC Drive Object, Instance 1, Attribute 28

Default: 0

Min.: -15

Max.: 15

224

B.15 Z: Bypass Parameters

356

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual