Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 351

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

Z1-11

(85D0) 2-Motor AND/OR

Function Select

2-Mtr AND/OR Sel

0: Disable

1: Always Mtr 1

2: Always Mtr 2

3: Alws Mtr 1 AND 2

4: OR DI HAND/

AUTO

5: OR 1 H DI AUTO

6: OR 2 H DI AUTO

7: AND/OR B DI

8: AND/OR 1 H DI A

9: AND/OR 2 H DI A

10: AND/OR B H DI A

0: Disabled (ignore digital inputs)

1: Always use only motor 1

2: Always use only motor 2

3: Always use motors 1 AND 2

4: OR function motor selected by digital input in HAND and

AUTO modes

5: OR function use motor 1 in HAND mode and motor selected

by digital input in AUTO mode

6: OR function use motor 2 in HAND mode and motor selected

by digital input in AUTO mode

7: AND/OR function motor selected (1, 2, or both) by (2) digital

inputs in HAND and AUTO mode

8: AND/OR function use motor 1 in HAND mode and motor

selected (1, 2, or both) by (2) digital inputs in AUTO mode

9: AND/OR function use motor 2 in HAND mode and motor

selected (1, 2, or both) by (2) digital inputs in AUTO mode

10: AND/OR function use motors 1 AND 2 in HAND mode and

motor selected (1, 2, or both) by (2) digital inputs in AUTO mode

Default: 0

Range: 0 to 10

210

Z1-12

(85D1) Run Delay Time

Run Delay Time

Delays the drive or bypass Run from when commanded (after

RUN, RUN ENABLE, and RUN INTERLOCK are all asserted).

Default: 0.0 s

Min.: 0.0

Max.: 300.0

210

Z1-13

(85D2) Pre-Interlock Run

Select

Pre Int Run Sel

0: Disable

1: Enable

Allows running at a preset speed starting immediately upon a Run

command, ignoring the BAS Interlock Input. The drive frequency

reference stays at this preset speed until the Run Delay time

(Z1-12) times out.

0: Disabled

1: Enable delay time only

Default: 0

Range: 0, 1

210

Z1-14

(85D3) Run Delay Frequency

Reference

Run Delay Fref

Frequency used while delaying the Run command.

Default: 60.0
Hz

<1>

Min.: 0.0

Max.: 60.0

210

Z1-15

(85D4) Interlock Wait Time

Interlck Wait

Upon entering a Run command, the damper actuator output will

be asserted. When an input is programmed for Interlock and the

time set to this parameter is reached before the Interlock input

goes active, a fault will be declared.

A setting of 0.0 will never time out.

Default: 0.0 s

Min.: 0.0

Max.: 300.0

210

Z1-24

(85DD) Contactor Open Delay

Time

Kx Open Delay

Sets the time to delay after commanding the drive output

contactor K2 or bypass contactor K3 or 2-Motor OR/AND

contactors K4 and K5 to open to allow the contacts to open.

Default: 0.2 s

Min.: 0.0

Max.: 5.0

212

Z1-25

(85DE) Contactor Close Delay

Time

Kx Close Delay

Sets the time to delay after commanding the drive output

contactor K2 or bypass contactor K3 or 2-Motor OR/AND

contactors K4 and K5 to close to allow the contacts to close.

Default: 0.2 s

Min.: 0.0

Max.: 5.0

213

Z1-27

(08E0) Phase Loss Brownout

Voltage Level

PL Brownout V

Sets the voltage level below which is considered a brownout

condition.

Default: 98 V

Min.: 0

Max.: 150

213

Z1-28

(85E1)

Phase Loss Brownout

Detection Time

PL Brownout T

PL Brownout T

Sets the time that the input voltage is continuously measured to

be below the Brownout Voltage level before declaring a

Brownout fault.

Default: 3.0 s

Min.: 0.0

Max.: 300.0

213

Z1-29

(85E2) Phase Loss Blackout

Voltage Level

PL Blackout V

Sets the voltage level below which is considered a blackout

condition. When the input voltage is measured below this level,

a Blackout fault will be declared.

Default: 0 V

Min.: 0

Max.: 150

213

Z1-30

(85E3) EF0 Fault Delay Time EF0 Flt Delay T

Sets the time between declaring a drive fault and opening the

drive and bypass contactors.

Default: 1.0 s

Min.: 0.0

Max.: 300.0

213

Z1-31

(85E4) Loss of Load Detection

Enable

Loss of Load En

0: Disable

1: Enable Fault

2: Enable Alarm

0: Disable

1: Enable and declare fault.

2: Enable and alarm only

Default: 0

Range: 0 to 2

213

Z1-32

(85E5) Loss of Load Drive

Frequency

Load Drive Freq

Sets the value to which the drive output frequency must be equal

to or greater than for the drive to detect a loss of load.

Default: 60.0
Hz

<1>

Min.: 0.0

Max.: 60.0

213

B.15 Z: Bypass Parameters

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

351

B

Parameter List