Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 256

Advertising
background image

HOA Keypad Display

Minor Fault Name

LT-2

Capacitor Maintenance Time

The main circuit and control circuit capacitors are nearing the end of their expected performance life.

Note:

An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.

Cause

Possible Solutions

The main circuit and control circuit capacitors have

reached 90% of their expected performance lives

Replace either the control board or the entire drive. For instructions on replacing the control board,

contact Yaskawa or your nearest sales representative.

HOA Keypad Display

Minor Fault Name

LT-3

Soft Charge Bypass Relay Maintenance Time
The DC bus soft charge relay is nearing the end of its expected performance life.

Note:

An alarm output (H2-oo = 10) will only be triggered if H2-oo = 2F.

Cause

Possible Solutions

The DC bus soft charge relay has reached 90% of

expected performance life

Replace either the control board or the entire drive. For instructions on replacing the control board,

contact Yaskawa or your nearest sales representative.

HOA Keypad Display

Minor Fault Name

oH

Heatsink Overheat
The temperature of the heatsink exceeded the overheat pre-alarm level set to L8-02 (90-100 °C).

Default value for L8-02 is determined by drive capacity (o2-04).

Cause

Possible Solutions

Surrounding temperature is too high

• Check the surrounding temperature.
• Improve the air circulation within the enclosure panel.
• Install a fan or air conditioner to cool surrounding area.
• Remove anything near drive that may cause extra heat.

Internal cooling fan has stopped

• Replace the cooling fan.
• After replacing the drive, set parameter o4-03 to 0 to reset the cooling fan operation time.

Airflow around the drive is restricted

• Provide proper installation space around the drive as indicated in the manual.

Refer to Installation

Orientation and Spacing on page 71

for details.

• Allow for the proper space and ensure that there is sufficient circulation around the control panel.
• Check for dust or other foreign materials clogging the cooling fan.
• Clear debris caught in the fan that restricts air circulation.

HOA Keypad Display

Minor Fault Name

oH2

Drive Overheat Warning
“Drive Overheat Warning” was input to a multi-function input terminal, S1 through S8 (H1-oo=

B).

Cause

Possible Solutions

An external device triggered an overheat warning

in the drive

Search for the device that tripped the overheat warning. Remove the cause of the problem.

HOA Keypad Display

Minor Fault Name

oH3

Motor Overheat
The motor overheat signal entered to a multi-function analog input terminal exceeded the alarm level

(H3-02 or H3-10 = E).

Cause

Possible Solutions

Motor thermostat wiring is faulty (PTC input).

Repair the PTC input wiring.

There is a fault on the machine side (e.g., the

machine is locked up)

• Check the status of the machine.
• Remove the cause of the fault.

6.5 Alarm Detection

256

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

Advertising