B.11 o: Operator-Related Settings

The o parameters set up the digital operator displays.

u

o1: HOA Keypad Display Selection

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

o1-03

(0502)

HOA Keypad Display

Selection

Display Unit Sel

0: 0.01 Hz

1: 0.01%

2: r/min

3: User Units

Sets the units the drive should use to display the frequency

reference and motor speed monitors.

0: 0.01 Hz

1: 0.01% (100% = E1-04)

2: r/min (calculated using the number of motor poles setting in

E2-04, E4-04, or E5-04)

3: User-selected units (set by o1-10 and o1-11)

Default: 0

Range: 0 to 3

195

o1-09

(051C)

Frequency Reference

Display Units

Fref Disp Unit

0: “WC

1: PSI

2: GPM

3: °F

4: CFM

5: CMH

6: LPH

7: LPS

8: Bar

9: Pa

10: °C

11: Mtr

12: Ft

13: LPM

14: CMM

16: No Unit

Sets unit display for the frequency reference parameters and

frequency related monitors when o1-03 > 40.

0: WC (Inch of water)

1: PSI (Pounds per square inch)

2: GPM (Gallons per minute)

3: F (Degrees Fahrenheit)

4: CFM (Cubic feet per minute)

5: CMH (Cubic meters per hour)

6: LPH (Liters per hour)

7: LPS (Liters per second)

8: Bar (Bar)

9: Pa (Pascal)

10: C (Degrees Celsius)

11: Mtr (Meters)

12: Ft (Feet)

13: LPM (Liters per minute)

14: CMM (Cubic meters per minute)

16: None

Default: 16

Range: 0 to 16

195

o1-10

(0520)

User-Set Display Units

Maximum Value

UserDisp Scaling

These settings define the display values when o1-03 is set to 3.

o1-10 sets the display value that is equal to the maximum output

frequency.

o1-11 sets the position of the decimal position.

Default:

<1>

Range: 1 to

60000

196

o1-11

(0521)

User-Set Display Units

Decimal Display

UserDisp Dec

Default:

<1>

Range: 0 to 3

196

<1> Default setting is dependent on parameter o1-03, HOA Keypad Display Selection.

u

o2: HOA Keypad Functions

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

o2-02

(0506)

OFF Key Function

Selection

Oper STOP Key

0: Disabled

1: Enabled

0: Disabled. OFF key is disabled in REMOTE operation.

1: Enabled. OFF key is always enabled.

Default: 1

Range: 0, 1

o2-04

(0508)

Drive Model Selection Inverter Model #

Enter the drive model. Setting required only if installing a new

control board.

Default:

Determined by

drive capacity

196

o2-06

(050A)

Operation Selection

when HOA Keypad is

Disconnected

Oper Discon Det

0: Disabled

1: Enabled

0: The drive continues operating if the HOA keypad is

disconnected.

1: An oPr fault is triggered and the motor coasts to stop.

Default: 1

Range: 0, 1

B.11 o: Operator-Related Settings

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

335

B

Parameter List