Drive

A1 Analog Input 1

0 or 4 to 20 mA

AC Analog input common

+V 10.5 V, 20 mA power supply

A2 Analog Input 2

A3 Analog Input 3

Jumper S1
A1/A2/A3
Voltage/Current
Selection

V

I

A1 A2 A3

Figure 5.54 Setting the Frequency Reference as a Current Signal to Terminal A2

Switching between Main/Auxiliary Frequency References

The frequency reference input can be switched between the analog terminals A1, A2, and A3 using multi-speed inputs.

Refer

to Multi-Step Speed Selection on page 156

for details on using this function.

Setting 2: BACnet, MEMOBUS/Modbus, P1, or N2 Communications

This setting requires entering the frequency reference via the RS-485 serial communications port (control terminals TXRX+

and TXRX-).

Setting 3: Option Card

This setting requires entering the frequency reference via an option board plugged into connector CN5 on the bypass control

board. Consult the option card manual for instructions on integrating the drive with the communication system.

n

Z1-08: Run Command Select

Determines the source of the Auto Mode RUN command used by the Bypass Controller.

No.

Name

Setting Range

Default

Z1-08

Run Command Select

1 to 3

1

Setting 0: HOA Keypad
Setting 1: Bypass Controller Digital Input

This setting requires entering the Run command via the digital input terminals.

Setting 2: BACnet, MEMOBUS/Modbus, P1, or N2 Communications

This setting requires entering the Run command via serial communications by connecting the RS-485 serial communication

cable to control terminals TXRX+ and TXRX- on the terminal block.

Refer to MEMOBUS/Modbus Configuration on page

382

for instructions.

Setting 3: Option Card

This setting requires entering the Run command via the communication option board by plugging a communication option

board into the CN5 port on the control PCB. Refer to the option card manual for instructions on integrating the bypass into

the communication system.

n

Z1-09: HAND Mode Drive Speed Reference

The speed reference used when the Drive is running in HAND mode.

No.

Name

Setting Range

Default

Z1-09

HAND Mode Drive Speed Reference

0.0 to 60.0 Hz

<1>

10.0 Hz

<1>

<1> Values are given in Hz, but actual values are dependent upon unit settings using drive parameters o1-03, o1-09, o1-10, and o1-11.

n

Z1-10: Smoke Purge Preset Frequency Reference

Sets the speed at which the drive will run when the Smoke Purge Drive input is active.

No.

Name

Setting Range

Default

Z1-10

Smoke Purge Preset Frequency Reference

0.0 to 60.0 Hz

<1>

10.0 Hz

<1>

<1> Values are given in Hz, but actual values are dependent upon unit settings using drive parameters o1-03, o1-09, o1-10, and o1-11.

5.14 Z: Bypass Parameters

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

209

5

Programming