Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 246

Advertising
background image

HOA Keypad Display

Fault Name

Motor has overheated

• Check the size of the load, the accel/decel times, and the cycle times.
• Decrease the load.
• Increase the acceleration and deceleration times (C1-01 and C1-02).
• Adjust the preset V/f pattern (E1-04 through E1-10) by reducing E1-08 and E1-10.
• Do not set E1-08 and E1-10 too low. This reduces load tolerance at low speeds.
• Check the motor rated current.
• Enter the motor rated current to parameter E2-01 as indicated on the motor nameplate.
• Ensure the motor cooling system is operating normally.
• Repair or replace the motor cooling system.

HOA Keypad Display

Fault Name

oH4

Motor Overheat Fault (PTC Input)
• The motor overheat signal to analog input terminal A1 or A2 exceeded the fault detection level.
• Detection requires setting multi-function analog inputs H3-02 or H3-10 to E.

Cause

Possible Solution

Motor has overheated

• Check the size of the load, the accel/decel times, and the cycle times.
• Decrease the load.
• Increase the acceleration and deceleration times (C1-01 and C1-02).
• Adjust the preset V/f pattern (E1-04 through E1-10) by reducing E1-08 and E1-10.
• Do not set E1-08 and E1-10 too low. This reduces load tolerance at low speeds.
• Check the motor rated current.
• Enter the motor rated current to parameter E2-01 as indicated on the motor nameplate.
• Ensure the motor cooling system is operating normally.
• Repair or replace the motor cooling system.

HOA Keypad Display

Fault Name

oL1

Motor Overload
The electronic motor overload protection tripped

Cause

Possible Solution

Load is too heavy

Reduce the load.

Note:

Reset oL1 when the U4-16 value falls below 100.0%. U4-16 value must be less than

100.0% before oL1 can be reset.

Cycle times are too short during acceleration and

deceleration

Increase the acceleration and deceleration times (C1-01 and C1-02).

A general-purpose motor is driven below the rated

speed with a high load

• Reduce the load.
• Increase the speed.
• If the motor is supposed to operate at low speeds, either increase the motor capacity or use a motor

specifically designed to operate in the desired speed range.

The output voltage is too high

• Adjust the user-set V/f pattern (E1-04 through E1-10) by reducing E1-08 and E1-10.
• Do not set E1-08 and E1-10 too low. This reduces load tolerance at low speeds.

The wrong motor rated current is set to E2-01

• Check the motor-rated current.
• Enter the motor rated current to parameter E2-01 as indicated on the motor nameplate.

The base frequency is set incorrectly

• Check the rated frequency indicated on the motor nameplate.
• Enter the rated frequency to E1-06 (Base Frequency).

The electrical thermal protection characteristics

and motor overload characteristics do not match

• Check the motor characteristics.
• Correct the type of motor protection that has been selected (L1-01).
• Install an external thermal relay.

The electrical thermal relay is operating at the

wrong level

• Check the current rating listed on the motor nameplate.
• Check the value set for the motor rated current (E2-01).

Motor overheated by overexcitation operation

• Overexcitation increases the motor loss and the motor temperature. Excessive duration of

overexcitation may cause motor damage. Prevent excessive overexcitation operation or apply

proper cooling to the motor.

• Reduce the excitation deceleration gain (n3-13).
• Set L3-04 (Stall Prevention during Deceleration) to a value other than 4.

6.4 Fault Detection

246

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

Advertising