5.14 Z: Bypass Parameters

Z parameters control bypass-specific functions.

u

Z1: Bypass Control System

n

Z1-01: Initialize

Sets parameters to default values.

No.

Name

Setting Range

Default

Z1-01

Initialize

0 to 3

0

Setting 0: No Initialize
Setting 1: Set all parameters to default values
Setting 2: Set only Bypass Controller parameters to default values
Setting 3: Set only Drive Controller parameters to default values

n

Z1-02: Password

Allows and restricts access to all parameters. Setting this value equal to the value in Z1-03 toggles access to all parameter

settings, except Z1-02. If the value entered to Z1-02 matches the value entered to Z1-03, the access to all parameters is denied

or granted.

No.

Name

Setting Range

Default

Z1-02

Password

n

Z1-03: Password Change

The value entered to this parameter is the password.

No.

Name

Setting Range

Default

Z1-03

Password Change

0 to 9999

0

n

Z1-05: Auto Transfer to Bypass Upon Drive Fault

Switches operation to Bypass mode when the drive is running and a drive fault occurs. When the fault is cleared, operation

will switch back to Drive mode

No.

Name

Setting Range

Default

Z1-05

Auto Transfer to Bypass Upon Drive Fault

0, 1

0

Setting 0: Disable
Setting 1: Enable

n

Z1-06: Power-Up Mode

Determines the mode of the Bypass Control upon power-up.

No.

Name

Setting Range

Default

Z1-06

Power-Up Mode

0 to 4

0

Setting 0: OFF

When drive powers up , it will be in “OFF” mode and will need an “AUTO” or “HAND” command to run.

Setting 1: AUTO-DRIVE

When drive powers up , the drive will get an “AUTO” command and needs an “OFF” command to stop.

Setting 2: HAND-DRIVE

When drive powers up , the drive will get a "HAND” command and needs an “OFF” command to stop.

Setting 3: AUTO-BYPASS

When drive powers up , the bypass will get an “AUTO” command and needs an “OFF” command to stop.

5.14 Z: Bypass Parameters

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

207