Table 5.4 PID Feedback Sources

PID Feedback Source

Settings

Analog Input A1

Set H3-02 = B

Analog Input A2

Set H3-10 = B

Analog Input A3

Set H3-06 = B

Pulse Input RP

Set H6-01 = 1

Note:

A duplicate allocation of the PID feedback input will cause an oPE alarm.

Differential Feedback

The second PID feedback signal for differential feedback can come from the sources listed in

Table 5.5

. The differential

feedback function is automatically enabled when a differential feedback input is assigned.

Table 5.5 PID Differential Feedback Sources

PID Differential Feedback Source

Settings

Analog Input A1

Set H3-02 = 16

Analog Input A2

Set H3-10 = 16

Analog Input A3

Set H3-06 = 16

Note:

A duplicate allocation of the PID differential feedback input will cause an oPE alarm.