Table 5.4 – Yaskawa Z1000U HVAC Matrix Bypass User Manual
Page 144

Table 5.4 PID Feedback Sources
PID Feedback Source
Settings
Analog Input A1
Set H3-02 = B
Analog Input A2
Set H3-10 = B
Analog Input A3
Set H3-06 = B
Pulse Input RP
Set H6-01 = 1
Note:
A duplicate allocation of the PID feedback input will cause an oPE alarm.
Differential Feedback
The second PID feedback signal for differential feedback can come from the sources listed in
. The differential
feedback function is automatically enabled when a differential feedback input is assigned.
Table 5.5 PID Differential Feedback Sources
PID Differential Feedback Source
Settings
Analog Input A1
Set H3-02 = 16
Analog Input A2
Set H3-10 = 16
Analog Input A3
Set H3-06 = 16
Note:
A duplicate allocation of the PID differential feedback input will cause an oPE alarm.
5.2 b: Application
144
YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual