H parameters: multi-function terminals, H1: multi-function digital inputs, B.8 h parameters: multi-function terminals – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 323

Advertising
background image

B.8 H Parameters: Multi-Function Terminals

H parameters assign functions to the multi-function input and output terminals.

u

H1: Multi-Function Digital Inputs

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

H1-03

(0400)

Multi-Function Digital

Input Terminal S3

Function Selection

Term S3 Func Sel

Assigns a function to the multi-function digital inputs through

Z2-oo = 3.

Refer to pages

165

to

167

for descriptions of setting values.

Note:

Set unused terminals to F.

Default: 24

Min.: 3

Max.: 60

165

H1-04

(0401)

Multi-Function Digital

Input Terminal S4

Function Selection

Term S4 Func Sel

Assigns a function to the multi-function digital inputs through

Z2-oo = 4.

Refer to pages

165

to

167

for descriptions of setting values.

Note:

Set unused terminals to F.

Default: 14

Min.: 3

Max.: 60

165

H1-05

(0402)

Multi-Function Digital

Input Terminal S5

Function Selection

Term S5 Func Sel

Assigns a function to the multi-function digital inputs through

Z2-oo = 5.

Refer to pages

165

to

167

for descriptions of setting values.

Note:

Set unused terminals to F.

Default: 3

Min.: 3

Max.: 60

165

H1-06

(0403)

Multi-Function Digital

Input Terminal S6

Function Selection

Term S6 Func Sel

Assigns a function to the multi-function digital inputs through

Z2-oo = 6.

Refer to pages

165

to

167

for descriptions of setting values.

Note:

Set unused terminals to F.

Default: 4

Min.: 3

Max.: 60

165

H1-07

(0404)

Multi-Function Digital

Input Terminal S7

Function Selection

Term S7 Func Sel

Assigns a function to the multi-function digital inputs through

Z2-oo = 7.

Refer to pages

165

to

167

for descriptions of setting values.

Note:

Set unused terminals to F.

Default: F

Min.: 3

Max.: 60

165

H1-08

(0405)

Multi-Function Digital

Input Terminal S8

Function Selection

Term S8 Func Sel

Assigns a function to the multi-function digital inputs through

Z2-oo = 8.

Refer to pages

165

to

167

for descriptions of setting values.

Note:

Set unused terminals to F.

Default: F

Min.: 3

Max.: 60

165

H1 Multi-Function Digital Input Selections

H1-oo

Setting

Function

LCD Display

Description

Page

0

3-Wire sequence

3-Wire Control

Closed: Reverse rotation (only if the drive is set up for 3-Wire sequence)

Terminals S1 and S2 are automatically set up for the Run command and Stop

command.

3

Multi-Step Speed

Reference 1

Multi-Step Ref 1

When input terminals are set to Multi-Step Speed References 1 through 3,

switching combinations of those terminals will create a multi-step speed sequence

using the frequency references set in d1-01 through d1-08.

165

4

Multi-Step Speed

Reference 2

Multi-Step Ref 2

When input terminals are set to Multi-Step Speed References 1 through 3,

switching combinations of those terminals will create a multi-step speed sequence

using the frequency references set in d1-01 through d1-08.

165

6

Jog reference selection

jog Freq Ref

Closed: Jog frequency reference (d1-17) selected. Jog has priority over all other

reference sources.

165

C

Analog terminal input

selection

Term A2 Enable

Open: Function assigned by H3-14 is disabled.

Closed: Function assigned by H3-14 is enabled.

165

8

Baseblock command

(N.O.)

Ext BaseBlk N.O.

Closed: No drive output

9

Baseblock command

(N.C.)

Ext BaseBlk N.C.

Open: No drive output

A

Accel/decel ramp hold

Acc/Dec RampHold

Open: Accel/decel is not held

Closed: The drive pauses during acceleration or deceleration and maintains the

output frequency.

B

Drive overheat alarm

(oH2)

OH2 Alarm Signal

Closed: Closes when an oH2 alarm occurs

F

Through mode

Term Not Used

Select this setting when using the terminal in a pass-through mode. The terminal

does not trigger a drive function, but it can be used as digital input for the controller

to which the drive is connected.

165

B.8 H Parameters: Multi-Function Terminals

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

323

B

Parameter List

Advertising