Table 3.3 Main Input Circuit Wiring Tightening Torques and Wire Gauges Without Option PW

Bypass Model Z1D1

Standard Circuit Breaker Without Option PW

208 Vac

480 Vac

Current Rating (A)

Wire Size Range (AWG)

Tightening Torque (lb. in.)

–

B011

25

14-10

or

8-3/0

50

or

120

–

B014

–

B021

40

D024

–

45

–

B027

50

D030

B034

60

–

B040

80

D046

B052

110

D059

B065

D074

B077

D088

B096

125

D114

–

175

4-4/0

225

D143

B124

200

–

B156

225

D169

B180

400

(1-2) x (2/0-500 kcmil)

(1-2) x 442

D211

–

–

B240

600

–

B032

–

B361

(1-3) x (3/0-500 kcmil)

(1-3) x 450

–

B414

Table 3.4 Motor and Ground Wire Gauges and Tightening Torques

Bypass Model Z1D1

Output Circuit Motor Wiring

Earth Ground Wiring

Motor Overload Relay

Ground Lug

208 Vac

480 Vac

Wire Size Range (AWG)

Tightening Torque

(lb. in.)

Wire Size Range (AWG)

Tightening Torque

(lb. in.)

–

B011

18-8

15

14-10 or 8

or

6-4 or 2

35 or 40

or

45 or 50

–

B014

D024

B021

D030

B027

–

B034

16-2

70

–

B040

D046

–

D059

B052

–

B065

10-1/0

100

D074

B077

D088

B096

6-3/0

200

D114

B124

D143

–

14-2/0

120

D169

B156

6–300 kcmil

275

–

B180

D211

B240

(1-2) x (2-600 kcmil)

(1-2) x 500

–

B302

–

B361

–

B414

(1-3) x (2-600 kcmil)

(1-3) x 500

3.4 Input and Output Power Wiring Connections

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

87

3

Electrical Installation