B.3 b: Application

Application parameters configure the source of the Run command, DC Injection Braking, Speed Search, timer functions, PID

control, Energy Savings, and a variety of other application-related settings.

u

b1: Operation Mode Selection

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

b1-01

(0180)

Frequency Reference

Selection for AUTO

mode

Ref Source 1

0: Operator

1: Analog Input

2: Serial Com

3: Option PCB

0: HOA keypad

1: Terminals (Analog Input Terminals)

2: Serial communications (APOGEE FLN, BACnet,

MEMOBUS/Modbus, or Metasys N2)

3: Option card

Default: 1

Range: 0 to 3

b1-02

(0181)

Run Command

Selection for AUTO

mode

Run Source 1

1: Digital Inputs

2: Communication

3: Option PCB

1: Control Circuit Terminal

2: Serial communications (APOGEE FLN, BACnet,

MEMOBUS/Modbus, or Metasys N2)

3: Option card

Default: 2

Range: 1 to 3

b1-03

(0182)

Stopping Method

Selection

Stopping Method

0: Ramp to Stop

1: Coast to Stop

2: DCInj to Stop

3: Coast w/Timer

0: Ramp to stop

1: Coast to stop

2: DC Injection Braking to stop

3: Coast with timer

Default: 1

Range: 0 to 3

133

b1-04

(0183)

Reverse Operation

Selection

Reverse Oper

0: Reverse Enabled

1: Reverse Disabled

0: Reverse enabled

1: Reverse disabled

Default: 1

Range: 0, 1

134

b1-08

(0187)

Run Command

Selection in

Programming Mode

RUN dur PRG Mode

0: Run

Disabled@PRG

1: ModeRun

Enabled@PRG

2: Prg only @ Stop

0: Run command is not accepted while in Programming Mode

1: Run command is accepted while in Programming

2: Prohibit entering Programming Mode during Run

Default: 0

Range: 0 to 2

b1-11

(01DF)

Drive Delay Time

Setting

Run Delay Time

After a Run command is entered, the drive output waits until

this delay time has passed before starting.

Default: 0 s

Min.: 0

Max.: 600

b1-14

(01C3) Phase Order Selection

Rotation Sel

0: Standard

1: SwitchPhaseOrder

0: Standard

1: Switch phase order (reverses the direction of the motor)

Default: 0

Range: 0, 1

b1-17

(01C6)

Run Command at Power

Up

Run Cmd @ Pwr On

0: Cycle Ext Run

1: Accept Ext Run

0: Disregarded.

A new Run command must be issued after power up.

1: Allowed.

Motor will start immediately after power up if a Run command

is already enabled.

Default: 1

Range: 0, 1

b1-24

(0B2C)

Commercial Power

Operation Switching

Selection

CommerclPwrSwSel

0: Disabled

1: Enabled

0: Disabled

1: Enabled

Default: 0

Range: 0, 1

135

b1-25

(0B2D)

Commercial Power

Supply Operation

Cancellation Level

Freq Deviate Lvl

Sets the judgement value of the hysteresis comparator in the

judgment section for the commercial power switching function

in increments of 0.1 Hz.

Default: 1.0 kHz

Min.: 0.4

Max.: 6.0

135

b1-26

(0B2E)

Commercial Power

Supply Operation

Switching Level

Freq Accept Lvl

Default: 0.2 kHz

Min.: 0.0

Max.: 3.0

135

u

b2: DC Injection Braking

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

b2-01

(0189)

DC Injection Braking

Start Frequency

DCInj Start Freq

Sets the frequency at which DC Injection Braking starts when

“Ramp to stop” (b1-03 = 0) is selected.

Default: 0.5 Hz

Min.: 0.0

Max.: 10.0

135

b2-02

(018A)

DC Injection Braking

Current

DCInj Current

Sets the DC Injection Braking current as a percentage of the

drive rated current.

Default: 50%

Min.: 0

Max.: 100

136

B.3 b: Application

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

311