Serial Communications

Refer to BACnet Communications on page 361

or

Refer to MEMOBUS/Modbus Communications on page 381

for details

depending on the applicable serial communications protocol.

n

Serial Communication Terminals

Table 3.9 Control Circuit Terminals: Serial Communications

Type

Name

Description

Notes

MEMOBUS/Modbus,

BACnet,

Metasys N2, or

Apogee P1

Communication

IG5

Isolated ground

Ground reference for RS-485 signals. This is an isolated ground

used only for communications and may be used in certain

circumstances to connect to other communication devices floating

ground references.

TXRX+

(+) Differential communication signal

RS-485 signal levels

TXRX-

(-) Differential communication signal

SHIELD Shield tie point

Connected to chassis ground

n

Bypass and Drive Control Circuit Wire Size and Torque Specifications

Select appropriate wire type and gauges from

Table 3.10

. For simpler and more reliable wiring, use crimp ferrules on the wire

ends. Refer to

Table 3.11

for ferrule terminal types and sizes.

Table 3.10 Bypass and Drive Control Circuit Gauge and Torque Values

Terminal

Screw

Size

Tightening

Torque

N

m

(lb. in)

Bare Wire Terminal

Ferrule-Type Terminal

Wire Type

Applicable

wire size

mm

2

(AWG)

Recomm.

wire size

mm

2

(AWG)

Applicable

wire size

mm

2

(AWG)

Recomm.

wire size

mm

2

(AWG)

DO-7, DO-8, DO-9,

DO-10

DI-1, DI-2, DI-3, DI-4,

DI-5, DI-6, DI-7, DI-8,

IG24

IG5, TXRX+, TXRX-,

SHIELD

M3

0.5 to 0.6

(4.4 to 5.3)

Stranded wire:

0.2 to 1.0

(24 to 16)

Solid wire:

0.2 to 1.5

(24 to 16)

0.75 (18)

0.25 to 0.5

(24 to 20)

0.5 (20)

Shielded wire,

etc.

+V, A1, A2, AC

FM, AM, AC

R+, R-, S+, S-, IG

M3

0.5 to 0.6

(4.4 to 5.3)

Stranded wire:

0.2 to 1.0

(24 to 16)

Solid wire:

0.2 to 1.5

(24 to 16)

0.75 (18)

0.25 to 0.5

(24 to 20)

0.5 (20)

Shielded wire,

etc.

n

Ferrule-Type Wire Terminals

Yaskawa recommends using CRIMPFOX 6, a crimping tool manufactured by PHOENIX CONTACT, to prepare wire ends

with insulated sleeves before connecting to the drive. See

Table 3.11

for dimensions.

d1

d2

8 mm

L

Figure 3.20 Ferrule Dimensions

Table 3.11 Ferrule Terminal Types and Sizes

Size mm

2

(AWG)

Type

L (mm)

d1 (mm)

d2 (mm)

Manufacturer

0.25 (24)

AI 0.25-8YE

12.5

0.8

1.8

PHOENIX CONTACT

0.34 (22)

AI 0.34-8TQ

10.5

0.8

1.8

0.5 (20)

AI 0.5-8WH or

AI 0.5-8OG

14

1.1

2.5