Setting parameters – Festo Электромотор MTR-DCI User Manual

Page 109

Advertising
background image

5. Commissioning

5-11

Festo P.BE-MTR-DCI-DN-EN en 1209a

Current limitation

1)

32

42

52

62

100 %

Z

1 x nominal motor current

Motor current
Motor torque

A
mNm

0.73
30

2.0
110

5.0
300

6.19
700

150 % (default)

Z

1.5 x nominal motor current

Motor current
Motor torque

A
mNm

1.1
46

3.0
171

7.5
460

9.29
1076

200 %

Z

2 x nominal motor current

Motor current
Motor torque

A
mNm

1.46
62

3.8

2)

220

7.7

2)

470

12.38
1450

1)

Parameter specification in FCT: relative motor current in % of nominal current. Setting range
10...200 %.

2)

Due to maximum current limiting the value does not rise further.

Tab. 5/3: Current limitation

Setting parameters

1. Select the homing parameters in the [Settings][Homing

parameter] menu (see Tab. 5/5).

2. Accept each setting with OK <Enter>. The setting will then

take effect in the drive.

3. Save the parameter settings with the

[SAVE] menu com-

mand.

} Settings

Homing parameter

Homing method
Velocity v_sw
Velocity v_s0
SAVE