3. Installation

3-10

Festo P.BE-MTR-DCI-DN-EN en 1209a

Logic voltage

In operation, the logic voltage is connected via the FBA-...
Fieldbus adapter

separately to the load voltage.

For MTR-DCI-42, 52, 62: For commissioning purposes, the
logic voltage can be optionally connected

together with the

load voltage via the power supply connection. In normal oper-
ation, the logic voltage

must be connected separately to the

load voltage via the FBA-... Fieldbus adapter.

With separate supply, the load voltage can be switched off
e.g. in the case of EMERGENCY-STOP, with logic voltage con-
tinuing to be applied and the controller remaining functional
and retaining its reference position.

Switch-on sequence

Do

not switch on the logic voltage after the load voltage,

since this may cause the MTR-DCI to switch off and back on
again (= reset).

Logic voltage failure

If the logic voltage fails, the controller will switch off.
For MTR-DCI-42, 52, 62: if the load voltage is still active, the
controller will switch back on but will lose its reference posi-
tion.

Logic voltage supply

32

42

52

62

In operation:
via Fieldbus adapter FBA-...

x

x

x

x

For commissioning and para-
meterisation:
optionally via the power supply
connection

x

x

x

Tab. 3/5: Logic voltage supply

Information on the connection specifications of the Fieldbus
adapter is provided in chapter 3.6.1 and also in the installa-
tion manual of the Fieldbus adapter.