4 diagnosis using fieldbus, 1 overview, 4 diagnosis using fieldbus 6.4.1 – Festo Электромотор MTR-DCI User Manual
Page 202

6. Diagnosis and error display
6-12
Festo P.BE-MTR-DCI-DN-EN en 1209a
6.4
Diagnosis using Fieldbus
6.4.1
Overview
The MTR-DCI supports the following diagnostic options over
DeviceNet:
–
Status bytes (access via FHPP, see section 5.5.2)
– SCON.B2: WARN – Warning
– SCON.B3: FAULT – Fault
– SPOS.B5: DEV
– Following error
– SPOS.B6: STILL – Standstill monitoring.
–
DeviceNet classes 101, 102, 108, 109.
DeviceNet class
INST
1)
ATTR
PNU
2)
See...
101
(65h)
Diagnostic mem-
ory
Diagnosis event
01h...10h
01h
200
Section
6.4.2
B.2.6
Malfunction number
01h...10h
02h
201
Timestamp
01h...10h
03h
202
102
(66h)
Diagnostic mem-
ory administration
–
Record fault
–
Resolution
–
Delete buffer
–
Number of entries
01h
01h
01h
01h
01h
02h
03h
04h
204
Section
B.2.6
108
(6Ch)
Current fault, warnings
01h
01h
205
Section
6.3 /
B.2.6
109
(6Dh)
Fieldbus dia-
gnostics
– Bus status
– Current bit rate
– Current MAC ID
– Current I/O data
length
01h
01h
01h
01h
01h
02h
04h
05h
206
Section
B.2.6
1) Access via Explicit Messaging
2) Access via I/O Messaging (FHPP-FPC)
Tab. 6/8: Diagnosis via Fieldbus: DeviceNet classes