5. Commissioning

5-20

Festo P.BE-MTR-DCI-DN-EN en 1209a

5.2.7

Setting bus parameters

Before commissioning on DeviceNet, valid bus parameters
must be set.

Station number (MAC-ID)

Valid station numbers: 0 ... 63.

The

invalid station number 255 is preset (control panel

display: ???).
This is to make sure that a correct address is set during
commissioning or when replacing.

Recommendation:
Assign the station numbers in ascending order. Adapt the
station numbering to the machinery infrastructure of your
plant.

Note
Station numbers can only be assigned once per Fieldbus
line.

Set the station numbers as follows:

1. Select [Settings] [Bus parameter] [MAC ID] (see also

section 4.5).

2. Press <Enter> to display the current setting.

3. Use the arrow keys to set the desired bit rate.

4. Accept the setting with OK “Enter”.

The set bit rate is saved permanently and protected
against network failure.

Note
The set bit rate will not take effect until

after a power off/

on process!

} Settings

Bus parameter

MAC ID

Baud rate

500 kBd

ESC ”Menu”

EDIT ”--”

OK ”Enter”