5. Commissioning

5-27

Festo P.BE-MTR-DCI-DN-EN en 1209a

5.4

Commissioning a DeviceNet master

The following sections describe the configuration and addres-
sing of the MTR-DCI on a DeviceNet interface or a DeviceNet
master. In order to understand this section you should be
familiar with DeviceNet and know the specification.

5.4.1

Overview of commissioning on the Fieldbus

The following steps are required for commissioning the
MTR-DCI as a Fieldbus station:

1. Configure the MTR-DCI:

on the control panel (MTR-DCI-...-H2 only, see sec-
tion 5.2.7), or

with the Festo Configuration Tool (see Festo
Configuration Tool Help).

Settings

Description

MAC-ID

Permissible participant address (station
number)
0 ... 63

Bit rate

Permissible bit rates:
500, 250, 125 kbit/s

I/O datalength

I/O data length
– 8 bytes (FHPP standard)
– 16 bytes (FHPP standard + FHPP-FPC)

Tab. 5/6: Fieldbus-specific parameters of the MTR-DCI

2. Configure master (see section 5.4.2):

Install EDS file, or

manually configure.

3. Test the Fieldbus connection in online mode.